Service/Boost Function Parameters
Description and selection
options
Alterna‐
tive
Modbus
address
Pass‐
word
level to
Read -
Write
Read
only
(RO) /
Read
Write
(RW) /
Write
(W)
Denes how to manage
when the opening degree
is outside of the threshold
of the max oset allowed
(ID30).
2: Once: If boosting for 15
seconds did not allow to get
back into position, then A9
alarm is raised and ICAD
goes to Safe state (ID20) (if
feasible), no calibration.
1: Cycling: Keep boosting 15
seconds, break for the time
specied as boost delay
(ID29), then raise A9 alarm.
Cycle continues position has
been regained.
Note: It is not recommen‐
ded to change this setting
from default.
Minutes after boost before
next boost and raise of A9
alarm. 1…30 minutes (min
step – 1)
Note: It is not recommen‐
ded to change this setting
from default.
Max oset value between
encoder position and step
counter position before
boosting starts. 3…15%
(min step – 1%)
Dene how to Reset/
Suppress A9 alarm and DO
Common Alarm ON.
2: Suppress: Ignore detec-
tion of the stall. No alarm is
raised and DO Common
Alarm output remains OFF.
1: Auto: Reset when it is
within max oset (ID30) limit
again and reset delay time
(ID32) has elapsed
0: Manually: User resets
alarm using the reset alarm
action.
Note: It is not recommen‐
ded to change this setting
from default.
Dene the reset delay for
A9 alarms. Only active
when reset A9 alarm (ID31)
is set to auto. 1…20 minutes
(min step – 1)
Note: It is not recommen‐
ded to change this setting
from default, and this value
should always be longer
than the boost delay (ID29)
ICM and ICMTS Motorized Valves with ICAD Actuators
© Danfoss | Climate Solutions | 2024.01 BC465027827472en-000102 | 24