Service/Display Parameters
Description and selection
options
Alterna‐
tive
Modbus
address
Pass‐
word
level to
Read -
Write
Read
only
(RO) /
Read
Write
(RW) /
Write
(W)
Manage the backlight level
of the built-in display on
ICAD 1...100%
(min step – 1%)
Manage the contrast level of
the built-in display on ICAD
1...100% (min step – 1%)
Service/Network Parameters, (RS485)
Description and selection
options
Alterna‐
tive
Modbus
address
Pass‐
word
level to
Read -
Write
Read
only
(RO) /
Read
Write
(RW) /
Write
(W)
Modbus RS485 network
address of ICAD
This is shown in display
when the ICAD supports
Modbus communication
and Modbus is enabled.
The baud rate your Modbus
RS485 controller uses to be
able to communicate with
ICAD via Modbus.
8: 115200
7: 57600;
6: 38400;
5: 19200;
4: 14400;
3: 9600;
2: 4800;
1: 2400;
0: 1200;
Set via com type on display:
2: 8E1: 8 bit even parity 1
stop bit 1:
1: 8E2: 8 bit even parity 2
stop bits
0: 8N1: 8 bit no parity 1 stop
bit
Other = custom setup via
Modbus
Modbus stops bits
1: 2 bits;
0: 1 bit
ICM and ICMTS Motorized Valves with ICAD Actuators
© Danfoss | Climate Solutions | 2024.01 BC465027827472en-000102 | 26