Label ID
Parameter
name
Description and selection
options
Min.
Max.
Factory set‐
ting
Modbus
address
Alterna‐
tive
Modbus
address
Size in
bytes
Pass‐
word
level to
Read -
Write
Read
only
(RO) /
Read
Write
(RW) /
Write
(W)
Persis‐
tent
Yes/No
Modbus
func‐
tion
ID140
A18
timestamp
(Warn: Vin
>24+10%)
Timestamp of the alarm oc-
currence relative to the run-
time counter (ID48),
Or -1 (0xFFFFFFFF in hex) if
the alarm is not set
-1
4294967294
4294967295
(-1,
or
0xFFFFFFFF
in hex)
3240 …
3241
3444 …
3445
4
1
RO
No
3
ID141
A19
timestamp
(Warn: Vin
<24-15%)
Timestamp of the alarm oc-
currence relative to the run-
time counter (ID48),
Or -1 (0xFFFFFFFF in hex) if
the alarm is not set
-1
4294967294
4294967295
(-1,
or
0xFFFFFFFF
in hex)
3242 …
3243
3446 …
3447
4
1
RO
No
3
ID146
A20
timestamp
(Alarm: De-
tection fail)
Timestamp of the alarm oc-
currence relative to the run-
time counter (ID48),
Or -1 (0xFFFFFFFF in hex) if
the alarm is not set
-1
4294967294
4294967295
(-1,
or
0xFFFFFFFF
in hex)
3244 …
3245
3448 …
3449
4
1
RO
No
3
ID148
A2(3)
timestamp
(Alarm: EE-
PROM opera-
tion fail)
Timestamp of the alarm oc-
currence relative to the run-
time counter (ID48),
Or -1 (0xFFFFFFFF in hex) if
the alarm is not set
-1
4294967294
4294967295
(-1,
or
0xFFFFFFFF
in hex)
3246 …
3247
3450 …
3451
4
1
RO
No
3
ID149
A2(4)
timestamp
(Alarm: Blue-
tooth MCU
comm fail)
Timestamp of the alarm oc-
currence relative to the run-
time counter (ID48),
Or -1 (0xFFFFFFFF in hex) if
the alarm is not set
-1
4294967294
4294967295
(-1,
or
0xFFFFFFFF
in hex)
3248 …
3249
3452 …
3453
4
1
RO
No
3
ID150
A3(5)
timestamp
(Alarm: Mod-
bus connec-
tion lost)
Timestamp of the alarm oc-
currence relative to the run-
time counter (ID48),
Or -1 (0xFFFFFFFF in hex) if
the alarm is not set
-1
4294967294
4294967295
(-1,
or
0xFFFFFFFF
in hex)
3250 …
3251
3454 …
3455
4
1
RO
No
3
ID152
A1(2)
timestamp
(Warn: Input
signal not
congured)
Timestamp of the alarm oc-
currence relative to the run-
time counter (ID48),
Or -1 (0xFFFFFFFF in hex) if
the alarm is not set
-1
4294967294
4294967295
(-1,
or
0xFFFFFFFF
in hex)
3252 …
3253
3456 …
3457
4
1
RO
No
3
Alarms/Event Log Parameters
Label ID
Parameter
name
Description and selection
options
Min.
Max.
Factory set‐
ting
Modbus
address
Alterna‐
tive
Modbus
address
Size in
bytes
Pass‐
word
level to
Read -
Write
Read
only
(RO) /
Read
Write
(RW) /
Write
(W)
Persis‐
tent
Yes/No
Modbus
func‐
tion
ID43
Stalls
Readout the total stalls
(times ICAD stopped due to
A9 alarms) done by the ICAD
from when it was rst pow-
ered on or factory reset.
Saved every 30min
0
32764
0
3120
3396
2
1
RO
Yes
3
ID46
Full strokes
Readout the total strokes
(movement) done by the
ICAD from when it was rst
powered on or factory reset.
Saved every 30min.
Full strokes are dened as
0% to 100% to 0% opening
degree.
0
4294967293
0
3121 ...
3122
3397 ...
3398
4
1
RO
Yes
3
ID230
Alarm
A9 (total
counter)
Total number of A9 alarms
for the ICAD is tracked.
0
32764
0
3124
3399
2
1
RO
Yes
3
© Danfoss | Climate Solutions | 2024.01 BC465027827472en-000102 | 33
ICM and ICMTS Motorized Valves with ICAD Actuators

Table of Contents

Other manuals for Danfoss ICM 25

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ICM 25 and is the answer not in the manual?

Danfoss ICM 25 Specifications

General IconGeneral
BrandDanfoss
ModelICM 25
CategoryControl Unit
LanguageEnglish

Related product manuals