Info
Description and selection
options
Alterna‐
tive
Modbus
address
Pass‐
word
level to
Read -
Write
Read
only
(RO) /
Read
Write
(RW) /
Write
(W)
Name assigned to ICAD as
the identication shown on
built-in display and for con-
nection via Bluetooth. 16
ASCII symbols, 8bits per
symbol
(2 symbols per register)
Readout the ICAD model
type.
3: ICADB TS
2: ICAD 1200B;
1: ICAD 600B;
0: not congured;
Readout the valve congura-
tion for ICAD
12: ICADBTS ICMTS 50/80;
11: ICADBTS ICMTS20;
10: Pilot Valve CVE;
9: ICAD1200B ICM150;
8: ICAD1200B ICM125;
7: ICAD1200B ICM100;
6: ICAD1200B ICM65;
5: ICAD1200B ICM50;
4: ICAD1200B ICM40;
3: ICAD600B ICM32;
2: ICAD600B ICM25;
1: ICAD600B ICM20;
0: not congured
Readout the sofware version
of ICAD nn.xx
Readout the sofware version
of ICAD xx.nn
Format MM.CC (1 byte Motor
PCB, 1 byte Connector PCB)
(e.g. value 0x0102 = 01.02v -
> 01 Motor PCB version, 02
Connector PCB version)
(reserved up to 0xFFFFFFFF)
Indicates if this ICAD has
previously been congured.
This controls when the setup
wizard is shown when con-
necting to ICAD via the APP.
1: congured;
0: not congured
The unique serial number of
ICAD. Number generated by:
nnnnnnnCCCCCCCCPPWWYY
- running number (n) +
Product number (Cs) + Mfg
place& time nnnnnnn part -
2 registers
CCCCCCCC PP parts - 5 regis-
ters, in ASCII symbols, 8bits
per symbol
(2 symbols per register)
WW part - 1 register
YY part - 1 register
D part - 1 register
Readout the run time in full
hours for the ICAD from
when it was rst powered on
or factory reset. Saved every
30min (in minutes)
© Danfoss | Climate Solutions | 2024.01 BC465027827472en-000102 | 35
ICM and ICMTS Motorized Valves with ICAD Actuators