Label ID
Parameter
name
Description and selection
options
Min.
Max.
Factory set‐
ting
Modbus
address
Alterna‐
tive
Modbus
address
Size in
bytes
Pass‐
word
level to
Read -
Write
Read
only
(RO) /
Read
Write
(RW) /
Write
(W)
Persis‐
tent
Yes/No
Modbus
func‐
tion
ID42
Temperature
Readout the internal tem-
perature measured on the
ICAD motor board in degree
celcius. -500...1400 points,
where 10 = 1°C (I.e. -125 =
-12.5°C;
1245 = 124.5°C)
-500
1400
0
3050
3334
2
1
RO
No
3
ID54
Bluetooth
Manage if ICAD broadcasts
Bluetooth for remote con-
nection via APP.
1: enable; 0: disable
0
1
1
3076
3361
1
1 - 2
RW
Yes
3 & 6, 16
ID237
Modbus
Enable/disable Modbus to
manage if data can be read
and set via Modbus connec-
tion. 1 = enable; 0 = disable
0
1
1
3104
3395
1
1 - 2
RW
Yes
3 & 6, 16
Alarms/Alarm Parameters
Label ID
Parameter
name
Description and selection
options
Min.
Max.
Factory set‐
ting
Modbus
address
Alterna‐
tive
Modbus
address
Size in
bytes
Pass‐
word
level to
Read -
Write
Read
only
(RO) /
Read
Write
(RW) /
Write
(W)
Persis‐
tent
Yes/No
Modbus
func‐
tion
ID120
A1
timestamp
(Warn: Valve
no cong)
Timestamp of the alarm oc-
currence relative to the run-
time counter (ID48),
Or -1 (0xFFFFFFFF in hex) if
the alarm is not set
[ID48 (while the device is
working)] - [event/alarm
timestamp (point in ID48 at
which the current event oc-
curred)] = minutes that have
passed since the event/
alarm occurred (to show XX
minutes(or hours) ago)
-1
4294967294
4294967295
(-1,
or
0xFFFFFFFF
in hex)
3200 …
3201
3404 …
3405
4
1
RO
No
3
ID121
A2(1)
timestamp
(Alarm: IO
MCU comm
fail)
Timestamp of the alarm oc-
currence relative to the run-
time counter (ID48),
Or -1 (0xFFFFFFFF in hex) if
the alarm is not set
-1
4294967294
4294967295
(-1,
or
0xFFFFFFFF
in hex)
3202 …
3203
3406 …
3407
4
1
RO
No
3
ID122
A2(2)
timestamp
(Alarm: Motor
open-load
status)
Timestamp of the alarm oc-
currence relative to the run-
time counter (ID48),
Or -1 (0xFFFFFFFF in hex) if
the alarm is not set
-1
4294967294
4294967295
(-1,
or
0xFFFFFFFF
in hex)
3204 …
3205
3408 …
3409
4
1
RO
No
3
ID123
A3(1)
timestamp
(Alarm: AI er-
ror: > 22 mA)
Timestamp of the alarm oc-
currence relative to the run-
time counter (ID48),
Or -1 (0xFFFFFFFF in hex) if
the alarm is not set
-1
4294967294
4294967295
(-1,
or
0xFFFFFFFF
in hex)
3206 …
3207
3410 …
3411
4
1
RO
No
3
ID124
A3(2)
timestamp
(Alarm: AI er-
ror: < 2 mA)
Timestamp of the alarm oc-
currence relative to the run-
time counter (ID48),
Or -1 (0xFFFFFFFF in hex) if
the alarm is not set
-1
4294967294
4294967295
(-1,
or
0xFFFFFFFF
in hex)
3208 …
3209
3412 …
3413
4
1
RO
No
3
ID125
A3(3)
timestamp
(Alarm: AI er-
ror: > 12 V)
Timestamp of the alarm oc-
currence relative to the run-
time counter (ID48),
Or -1 (0xFFFFFFFF in hex) if
the alarm is not set
-1
4294967294
4294967295
(-1,
or
0xFFFFFFFF
in hex)
3210 …
3211
3414 …
3415
4
1
RO
No
3
ID126
A3(4)
timestamp
(Alarm: AI er-
ror: < 1 V)
Timestamp of the alarm oc-
currence relative to the run-
time counter (ID48),
Or -1 (0xFFFFFFFF in hex) if
the alarm is not set
-1
4294967294
4294967295
(-1,
or
0xFFFFFFFF
in hex)
3212 …
3213
3416 …
3417
4
1
RO
No
3
© Danfoss | Climate Solutions | 2024.01 BC465027827472en-000102 | 31
ICM and ICMTS Motorized Valves with ICAD Actuators

Table of Contents