Service/System Parameters
Label ID
Parameter
name
Description and selection
options
Min.
Max.
Factory set‐
ting
Modbus
address
Alterna‐
tive
Modbus
address
Size in
bytes
Pass‐
word
level to
Read -
Write
Read
only
(RO) /
Read
Write
(RW) /
Write
(W)
Persis‐
tent
Yes/No
Modbus
func‐
tion
ID49
Service
reminder
Use a service reminder for
when the valve should be
serviced in order to maintain
operation of the system.
ICAD will initiate a warning
when Time to next service
(ID50) reaches 0. Valves
should be checked once a
year. This is enabled by de-
fault. 1: ON; 0: OFF
0
1
0
3062
3349
1
1 - 2
RW
Yes
3 & 6, 16
ID51
Reset service
interval
Use a service reminder for
when the valve should be
serviced in order to maintain
operation of the system.
ICAD will initiate a warning
when Time to next service
(ID50) reaches 0. Valves
should be checked once a
year. This is enabled by de-
fault. 1: ON; 0: OFF
0
1
0
3066
1
2 - 2
RW
No
3 & 6, 16
ID234
Service
interval
Indicates the service interval
until the valve should be
checked. This is by default
once a year. 1…999 (in days)
1
999
365
3065
3352
2
1 - 2
RW
Yes
3 & 6, 16
ID26
Clear event
log
Clear event log
1: Yes: All event log entries
will be hidden. The parame-
ter will automatically be set
back to ‘no’ when hide has
nished
0: No: Not active
0
1
0
3123
1
2 - 2
RW
No
3
ID52
User logout
time
The time user remains log-
ged in to service mode with-
out doing any actions before
automatically logged out
30…1200 (in seconds)
30
1200
360
3067
2
2 - 2
RW
Yes
3 & 6, 16
ID53
ICAD name
Name assigned to ICAD as
the identication shown on
built-in display and for con-
nection via Bluetooth. 16
ASCII symbols, 8bits per
symbol
(2 symbols per register)
ICAD
3068 …
3075
3353 …
3360
30
1 - 2
RW
Yes
3 & 6, 16
ID54
Bluetooth
enable
Enable ICAD to broadcast
Bluetooth for remote con-
nection via APP.
1: enable; 0: disable
0
1
1
3076
3361
1
1 - 2
RW
Yes
3 & 6, 16
ID236
Factory reset
Factory reset action for
ICAD
1: Yes: All parameters will be
returned to factory default
settings, and the event log
will be cleared. The parame-
ter will automatically be set
back to ‘no’ when factory re-
set has nished
0: No: Not active
0
1
0
3087
1
2 - 2
RW
No
3 & 6, 16
© Danfoss | Climate Solutions | 2024.01 BC465027827472en-000102 | 25
ICM and ICMTS Motorized Valves with ICAD Actuators

Table of Contents

Other manuals for Danfoss ICM 25

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ICM 25 and is the answer not in the manual?

Danfoss ICM 25 Specifications

General IconGeneral
BrandDanfoss
ModelICM 25
CategoryControl Unit
LanguageEnglish

Related product manuals