Description and selection
options
Alterna‐
tive
Modbus
address
Pass‐
word
level to
Read -
Write
Read
only
(RO) /
Read
Write
(RW) /
Write
(W)
Readout of boost action.
How to manage when the
opening degree is outside of
the threshold of the max o-
set allowed (ID30).
2:Once: If boosting for 15
seconds did not allow to get
back into position, then A9
alarm is raised and ICAD
goes to Safe state (ID20) (if
feasible), no calibration.
1: Cycling: Keep boosting
15 seconds, break for the
time specied as boost de-
lay (ID29), then raise A9
alarm. Cycle continues posi-
tion has been regained.
Note: It is not recommended
to change this setting from
default.
Readout of boost delay. Mi-
nutes after boost before
next boost and raise of A9
alarm.
1…30 minutes (min step – 1)
Note: It is not recommended
to change this setting from
default.
Max oset value between
encoder position and step
counter position before
boosting starts. 3…15%
(min step – 1%)
Dene how to Reset/
Suppress A9 alarm and DO
Common Alarm ON.
2: Suppress: Ignore detec-
tion of the stall. No alarm is
raised and DO Common
Alarm output remains OFF.
1: Auto: Reset when it is
within max oset (ID30) limit
again and reset delay time
(ID32) has elapsed
0: Manually: User resets
alarm using the reset alarm
action.
Note: It is not recommended
to change this setting from
default.
Dene the reset delay for A9
alarms. Only active when re-
set A9 alarm (ID31) is set to
auto. 1…20 minutes (min
step – 1)
Note: It is not recommen‐
ded to change this setting
from default, and this value
should always be longer
than the boost delay (ID29)
ICM and ICMTS Motorized Valves with ICAD Actuators
© Danfoss | Climate Solutions | 2024.01 BC465027827472en-000102 | 30