Description and selection
options
Alterna‐
tive
Modbus
address
Pass‐
word
level to
Read -
Write
Read
only
(RO) /
Read
Write
(RW) /
Write
(W)
Shows active alarms (e.g.
value 0x00000406 = 0000
0000 0000 0000 0000 0100
0000 0110 -> alarms A2, A3,
A8 have been set and active)
0th bit: A2 (IO MCU comm
fail);
1st bit: A2 (open-load sta-
tus);
2nd bit: A3 (AI error: > 22
mA);
3rd bit: A3 (AI error: < 2
mA);
4th bit: A3 (AI error: > 12 V);
5th bit: A3 (AI error: < 1 V);
6th bit: A4 (V FSS error);
7th bit: A5 (V PS error);
8th bit: A6 (Calibr fail);
9th bit: A7 (Overheating);
10th bit: A8 (Overheating);
11th bit: A9 (POM mode);
12th bit: A10 (SPI conn loss);
13th bit: A13 (Failed up-
date);
14th bit: A20 (Detection
fail);
15th bit: A2 (EEPROM oper-
ation fail);
16th bit: A2 (Bluetooth MCU
comm fail);
17th bit: A3 (Modbus con-
nection lost)
Shows active warnings 0th
bit: A1 (Valve not cong);
1st bit: A11 (reserved);
2nd bit: A14 (SoH is bad);
3rd bit: A15 (Service over-
due);
4th bit: A16 (Cong. mode);
5th bit: A17 (Bluetooth
conn);
6th bit: A18 (Vin >24+10%);
7th bit: A19 (Vin <24-15%);
8th bit: A1 (Input not con-
g)
Total number of events in
the event log
(the maximum value is
changeable, depends on the
types of events in the event
log)
The event log stores the last
events, including historic
alarms, logins and congura-
tion changes.