3.3.7 EMC-correct Electrical Installation
General points to observe to ensure EMC-correct electrical installation:
Use only screened/armoured motor cables and screened/armoured control cables.
Connect the screen to ground at both ends.
Avoid installation with twisted screen ends (pigtails), since this ruins the screening effect at high frequencies. Use
cable clamps instead.
Ensure good electrical contact from the installation plate through the installation screws to the metal cabinet of
the frequency converter.
Use starwashers and galvanically conductive installation plates.
Do not use unscreened/unarmoured motor cables in the installation cabinets.
Illustration 3.17 shows EMC-correct electrical installation, in which the frequency converter has been fitted in an installation
cabinet and connected to a PLC.
Illustration 3.17 Example of an EMC-correct Electrical Installation
Installation Design Guide
MG27E402 Danfoss A/S © Rev. May/2014 All rights reserved. 41