3.4.20 Sub D Plug
Illustration 3.36 Sub D Plug
An LCP 2 control unit can be connected to the Sub D plug
on the control card. The ordering number of LCP 2 Control
Unit is 175N0131.
LCP control unit with ordering number 175Z0401 cannot
be connected to Sub D plug.
3.5
Connection Examples
3.5.1 Start/Stop
Start/stop using terminal 18 and coasting stop using
terminal 27.
•
Parameter 302 Digital input=[7] Start
•
Parameter 304 Digital input=[2] Coasting stop
inverted
For Precise start/stop the following settings are made:
•
Parameter 302 Digital input=[27] Precise start/stop
•
Parameter 304 Digital input=[2] Coasting stop
inverted
Illustration 3.37 Start/Stop Connection
3.5.2 Pulse Start/Stop
Pulse start using terminal 18 and pulse stop using terminal
19. In addition, the jog frequency is activated via terminal
29.
•
Parameter 302 Digital input=[8] Pulse start
•
Parameter 303 Digital input=[6] Stop inverted
•
Parameter 304 Digital input=[2] Coasting stop
inverted
•
Parameter 305 Digital input=[13] Jog
Illustration 3.38 Pulse Start/Stop Connection
Installation Design Guide
56 Danfoss A/S © Rev. May/2014 All rights reserved. MG27E402
33