3.3.8 Use of EMC Compliant Cables
To comply with requirements for EMC immunity of the control cables and EMC emissions for the motor cables, use
screened/armoured cables.
The ability of a cable to reduce the amount of ingoing and outgoing radiation of electric noise depends on the transfer
impedance (Z
T
). The screen of a cable is normally designed to reduce the transfer of electric noise, and a screen with a
lower Z
T
is more effective than a screen with a higher Z
T
.
Z
T
is rarely stated by cable manufacturers, but it is often possible to estimate Z
T
by looking at and assessing the physical
design of the cable.
Z
T
can be assessed on the basis of the following factors:
The contact resistance between the individual screen conductors.
Screen coverage, i.e. the physical area of the cable covered by the screen. Is often stated as a percentage and
should be no less than 85%.
The screen type, i.e. braided or twisted pattern. A braided pattern or closed pipe is recommended.
Illustration 3.18 Cable Comparison
Installation Design Guide
42 Danfoss A/S © Rev. May/2014 All rights reserved. MG27E402
33

Table of Contents

Other manuals for Danfoss VLT 2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 and is the answer not in the manual?

Danfoss VLT 2800 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2800
CategoryDC Drives
LanguageEnglish

Related product manuals