FC 300 Design Guide
How to Program
3-51 Ramp 2 Ramp-up Time
Range:
0.01 - 3600.00 s
*
s
Function:
The ramp-up time is the accele ration time from
0 RPM to the rated motor speed n
M,N
(par.
1-23). The output current must not reach the
torque limit (set in p a r. 4-16). The value 0.00
corresponds to 0.01 sec. in speed mode.
3-52 Ramp 2 Ramp-down Time
Range:
0.01 - 3600.00 s.
*
s
Function:
The ramp-down time is the dec eleration time from
the rated motor speed n
M,N
(par. 1-23) to 0 RPM.
Theremustbenoovervoltageintheinverter
because of regenerative operation of the m otor, nor
can the generated current reach the torque lim it
(set in par. 4-17). The value 0.00 corr esponds to
0.01 s in speed m o de. See ramp in par. 3-51.
3-55 Ramp 2 S-ramp Ratio at A ccel. Start
Range:
1 - 99%
*
50%
Function:
Set the per iod of the total ramp-up time (par. 3-51)
where the acceleration torque is growing smoothly.
A large percentage minimizes torq ue je rks.
3-56 Ramp 2 S-ramp Ratio at Accel. End
Range:
1-99%
*
50%
Function:
Set the period of the total ram-up time (par. 3 -51)
where the acceleration torque is declining smoothly.
A large percentage minimizes torq ue je rks.
3-57 Ramp 2 S-ramp Ratio at Decel. Start
Range:
1-99%
*
50%
Function:
Set the period of the total ramp-down time
(par. 3-5 2) where the de cele ration torque
is growing smoothly. A large percentage
minimizes torque jerks.
3-58 Ramp 2 S -ram p Ratio at Decel. End
Range:
1-99%
*
50%
Function:
Set the period of the total ramp-down time
(par. 3-5 2) where the de cele ration torque
is declining smoothly. A large percentage
minimizes torque jerks.
" 3-6* Ramp 3
3-60 Ramp 3 Type
Option:
*
Linear [0]
Function:
Selects the desired ramp type, depending on
requirements for acceleration/deceleration.
*
default setting ()display text []value for use in communication via serial communication port
158
MG.33.B
3.22 - VLT is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 Series and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals