FC 300 Design Guide
How to Program
Function:
The ramp-up time is the acceleration time from 0
RPM to the rated motor speed nM,N (par. 1-23),
provided that the output current does not reach
thetorquelimit(setinpar. 4-16). Thevalue0.00
corresponds to 0.01 s in speed mode.
3-42 Ramp 1 Ramp-down Time
Range:
0.01 - 3600.00 s
*
ExpressionLimits
Function:
The ramp-down time is the dec eleration time from
the rated motor speed n
M,N
(par. 1-23) to 0 RPM,
provided that there is no over-voltage in t h e inverter
due to regenerative operation of the motor, or if the
generated current reaches the torque limit (set in
par. 4-17). The value 0.00 corresponds to 0.01 s in
speed mode. See ramp-up time in par. 3-41
3-45 Ramp 1 S-ramp Ratio at A ccel. Start
Range:
1 - 99%
*
50%
Function:
Set the period of the total ramp-up time (par. 3-41)
where the acce leration torque is growing smoothly.
A large percentage minimizes torque jerks.
3-46 Ramp 1 S-ramp Ratio at Accel. End
Range:
1-99%
*
50%
Function:
Set the per iod of the total ramp-up time (par. 3-41)
where the acceleration torque is declining smoothly.
A large percentage minimizes torq ue je rks.
3-47 Ramp 1 S-ramp Ratio at Decel. Start
Range:
1-99%
*
50%
Function:
Set the period of the total ramp-down time
(par. 3-4 2) where the de cele ration torque
is growing smoothly. A large percentage
minimizes torque jerks.
3-48 Ramp 1 S -ram p Ratio at Decel. End
Range:
1-99%
*
50%
Function:
Set the period of the total ramp-down time
(par. 3-4 2) where the de cele ration torque
is declining smoothly. A large percentage
minimizes torque jerks.
" 3-5* Ramp 2
3-50 Ramp 2 Type
Option:
*
Linear [0]
Function:
Selects the desired ramp type, depending on
requirements for acceleration/deceleration.
*
default setting ()display text []value for use in communication via serial communication port
157
MG.33.B
3.22 - VLT is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 Series and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals