400 msec. the resulting reference will ramp
youaccordingtoRamp2(par. 3-41).
Slow-down Catch up
Unchanged speed 0 0
Reduced by %-value 1 0
Increased by %-value 0 1
Reduced by %-value 1 1
• Slow-down [29]:SameasCatchup[28].
• Pulse input [32]: Selec t Pulse inpu t if you
useapulsesequenceaseitherreferenceor
feedback. Scaling is done in par. group 5-5* .
• Ramp bit 0 [34]
• Ramp bit 1 [35]
• Mains failu re inverse [36]:Isselectedto
activate par. 14-10 Mains Failure. Mains fa ilure
inverseisactiveintheLogic’0’situation.
• DigiPot increase [55]: Usestheinputasan
INCREASE signal to the Di gital Potentiometer
function described in parameter g roup 3-9*
• DigiPot decrease [56]: Usestheinputasa
DECREASE sig n al to the Digital Potentiometer
function described in parameter g roup 3-9*
• DigiPot clear [57]:Usestheinputto
CLEAR the Digital Potentiometer reference
described in parameter group 3-9*
• Counter A (up) [60]: (Terminal 29 only) Inp ut
for increment counting in the SLC counter.
• Counter A (down) [61]: (Terminal 29 only)
Input for decrement counting in the SLC counter.
• Reset Counter A [62]: Input for
reset of counter A.
• Counter B (up) [63]: (Te rm inal 29 only) Input
for increment counting in the SLC counter.
• Counter B (down) [64]: (Terminal 29 only)
Input for decrement counting in the SLC counter.
• Reset Counter B [65]: Input for
reset of counter B.
• Slow [22]: S am e as Speed up [21].
• Set-up select bit 0 [23] : Selection of
Set-up, bit 0 and bit 1 provid es the ability to
choose between one of the four set-ups. You
must set par. 0-10 to Multi setup.
• Set-up select bit 1 [24] (Default Digital input
32): Same as Set-up select bit 0 [23].
• Catch up [28]:SelectCatchup/Slow-down
to increase or reduce the re ference value
(set in par. 3-12).
5-10 Terminal 18 Digital Input
*
Start [8]
Function:
5-11 Terminal 19 Digital Input
*
Reverse [10]
5-12 Terminal 27 Digital Input
*
Coast inverse [2]
5-13 Terminal 29 Digital Input
*
Jog [14]
5-14 Terminal 32 Digital Input
*
No operation [0]
5-15 Terminal 33 Digital Input
*
No operation [0]
"
5-3* Digital Outputs
The 2 solid-state digital outputs are common
for terminals 27 and 29. Set the I/O function
for terminal 27 in pa r. 5-01, and set the I/O
function for terminal 29 in par. 5-02.
These parameters cannot be set while running.
No operation [0]
Control ready [1]
Drive ready [2]
Drive ready / remote [3]
Enable / no warning [4]
VLT running [5]
Running / no warning [6]
Runinrnge,nowarn [7]
Runonref.,nowarn. [8]
Alarm [9]
Alarm or warning [10]
At torque limit [11]
Out of current range [12]
Below current, low [13]
Above c urrent, high [14]
Out of speed range [15]
Belowspeed,low [16]
Above speed, high [17]
Thermal warning [21]
Ready, no thrm warn [22]
Rmte rdy, no th wrn [23]
*
default setting ()display text []value for use in communication via serial communication port