FC 300 Design Guide
How to Program
400 msec. the resulting reference will ramp
youaccordingtoRamp2(par. 3-41).
Slow-down Catch up
Unchanged speed 0 0
Reduced by %-value 1 0
Increased by %-value 0 1
Reduced by %-value 1 1
• Slow-down [29]:SameasCatchup[28].
• Pulse input [32]: Selec t Pulse inpu t if you
useapulsesequenceaseitherreferenceor
feedback. Scaling is done in par. group 5-5* .
• Ramp bit 0 [34]
• Ramp bit 1 [35]
• Mains failu re inverse [36]:Isselectedto
activate par. 14-10 Mains Failure. Mains fa ilure
inverseisactiveintheLogic’0’situation.
• DigiPot increase [55]: Usestheinputasan
INCREASE signal to the Di gital Potentiometer
function described in parameter g roup 3-9*
• DigiPot decrease [56]: Usestheinputasa
DECREASE sig n al to the Digital Potentiometer
function described in parameter g roup 3-9*
• DigiPot clear [57]:Usestheinputto
CLEAR the Digital Potentiometer reference
described in parameter group 3-9*
• Counter A (up) [60]: (Terminal 29 only) Inp ut
for increment counting in the SLC counter.
• Counter A (down) [61]: (Terminal 29 only)
Input for decrement counting in the SLC counter.
• Reset Counter A [62]: Input for
reset of counter A.
• Counter B (up) [63]: (Te rm inal 29 only) Input
for increment counting in the SLC counter.
• Counter B (down) [64]: (Terminal 29 only)
Input for decrement counting in the SLC counter.
• Reset Counter B [65]: Input for
reset of counter B.
• Slow [22]: S am e as Speed up [21].
• Set-up select bit 0 [23] : Selection of
Set-up, bit 0 and bit 1 provid es the ability to
choose between one of the four set-ups. You
must set par. 0-10 to Multi setup.
• Set-up select bit 1 [24] (Default Digital input
32): Same as Set-up select bit 0 [23].
• Catch up [28]:SelectCatchup/Slow-down
to increase or reduce the re ference value
(set in par. 3-12).
5-10 Terminal 18 Digital Input
*
Start [8]
Function:
5-11 Terminal 19 Digital Input
*
Reverse [10]
5-12 Terminal 27 Digital Input
*
Coast inverse [2]
5-13 Terminal 29 Digital Input
*
Jog [14]
5-14 Terminal 32 Digital Input
*
No operation [0]
5-15 Terminal 33 Digital Input
*
No operation [0]
"
5-3* Digital Outputs
The 2 solid-state digital outputs are common
for terminals 27 and 29. Set the I/O function
for terminal 27 in pa r. 5-01, and set the I/O
function for terminal 29 in par. 5-02.
These parameters cannot be set while running.
No operation [0]
Control ready [1]
Drive ready [2]
Drive ready / remote [3]
Enable / no warning [4]
VLT running [5]
Running / no warning [6]
Runinrnge,nowarn [7]
Runonref.,nowarn. [8]
Alarm [9]
Alarm or warning [10]
At torque limit [11]
Out of current range [12]
Below current, low [13]
Above c urrent, high [14]
Out of speed range [15]
Belowspeed,low [16]
Above speed, high [17]
Thermal warning [21]
Ready, no thrm warn [22]
Rmte rdy, no th wrn [23]
*
default setting ()display text []value for use in communication via serial communication port
168
MG.33.B
3.22 - VLT is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 Series and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals