FC 300 Design Guide
How to Program
Ready, voltage OK [24]
Reverse [25]
Bus OK [26]
Torqu e limit stop [27]
Brake, no warning [28]
Brake ready, no fault [29]
Brake fault (IGBT) [30]
Relay 123 [31]
Mech. brake control [32]
Safe stop active [33]
MCO controlled [51]
Comparator 0 [60]
Comparator 1 [61]
Comparator 2 [62]
Comparator 3 [63]
Logic rule 0 [70]
Logic rule 1 [71]
Logic rule 2 [72]
Logic rule 3 [73]
SL digital output A [80]
SL digital output B [81]
SL digital output C [82]
SL digital output D [83]
SL digital output E [84]
SL digital output F [85]
Local ref. active [120]
Remote ref. active [121]
No alarm [122]
Start cmd. active [123]
Running reverse [124]
Drive in hand mode [125]
Drive in auto mode [126]
You can program the digital outputs to
these functions:
• No operation [0]: Default for all digital
outputs and relay outputs
• Control ready [1]: The control board
receives supply voltage.
• Drive ready [2]: The adjustable frequency
drive is ready for operation and applies a
supply signal on the control board.
• Driveready/remote[3]: The adjustable
frequency drive is ready for operation
andisinAutoOnmode.
• Enable / no warning [4]:Theadjustable
frequency drive is ready for use. No start or
stop command has been given (start/disab
le).
There are no warnings.
• VLT running [5]: The motor is running.
• Running / no warning [6]:Theoutputspe
ed
is higher than the speed set in par. 1-81 . The
motor is running and there are no warnings.
• Runinrnge,nowarn[7]: Runs within
the programmed cur rent/speed ranges set
in p ar. 4-50 to par. 4-53.
• Run on ref., no warn. [8]: Mechanical
speed according to reference.
• Alarm [9]: An alarm activates the output.
• Alarm or warning [10]:Analarmora
warning activates the output.
• At torque limit [11]: The torque limit set in
p a r. 4 - 1 6 o r p a r. 1 - 1 7 i s e xc e e d e d .
• Out of current range [12]: The motor current
is outside the range set in par. 4-18.
• Below current, low [13]: The motor current
is lower than set in par. 4-50.
• Above c urrent, high [14]: The motor current
is higher than set in par. 4-51.
• Out of speed range [15]
• Below speed, low[16]: The output speed
is lower than set in par. 4-52.
• Above speed, high [17]: The output speed
is higher than set in par. 4-53.
• Thermal warning [21]: Thermal warning
is on when the temperature is above limit in
the motor, the adjustable frequency drive, the
brake resistor, or the thermistor.
• Ready, no thrm warn [22]: The adjustable
frequency d rive is ready for operation and
there is no overtemperature warning.
• Rmte rdy, no th w r n [23]: The adjustable
frequency drive is ready for operation
andisinAutoOnmode. Thereisno
overtemperature warning.
• Ready, voltage OK [24]: The adjustable
frequency drive is ready for operation and the
line voltage is within the specified voltage range
(see section General Specifications).
• Reverse [25]: Reversing. Logic ’1’ = relay
activated, 24 V DC when CW rotation of the
motor. Logic ’0’ = relay not activated, no signal,
when CCW rotation of the motor.
• Bus OK [26] : Active communication (no
timeout) via the serial communication port.
• Torque limit stop [27] :Isusedwhen
performing a coasting stop and in torque
limit condition. If the adjustable frequency
drive has received a stop signal and is at the
torque limit, the signal is Lo gic ’0’.
• Brake, no warning [28]:Thebrakeis
active and there are no warnings.
*
default setting ()display text []value for use in communication via serial communication port