FC 300 Design Guide
How to Program
Brake ready, no fault [29]:Thebrakeis
ready for operation and there are no faults.
Brake fault (IGBT) [30]: The output is Logic
"1" when the brake IGBT is short-circuited. Use
this function to protect the a djustable frequency
drive if there is a fault on the brake modules.
Use the output/ relay to cut out the line voltage
from the adjus table frequency drive.
Relay 123 [31]: If Fieldbus profile [0]
is selected in par. 5-12, the relay is
activate. If OFF1, OFF2 or OFF3 (bit in
the control word) is Logic ’1’.
Mech. brake control [32]:Enables
control of an external mechanical brake, see
description in the section Co ntrol of Mechanical
Brake,andpar. group2-2*
Safe stop active [33]: Indicates that the safe
stop on terminal 37 has been activated.
MCO controlled [51]
Comparator 0 [60]: See par. group 13-1*. If
Comparator 0 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Comparator 1 [61]: See par. group 13-1*. If
Comparator 1 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Comparator 2 [62]: See par. group 13-1*. If
Comparator 2 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Comparator 3 [63]: See par. group 13-1*. If
Comparator 3 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
Logic Rule 0 [70]: See par. group 13-4*. If
Logic Rule 0 is evaluated a s TRUE, the output
will go high. Otherwise, it will be low.
Logic Rule 1 [71]: See par. group 13-4*. If
Logic Rule 1 is evaluated a s TRUE, the output
will go high. Otherwise, it will be low.
Logic Rule 2 [72]: See par. group 13-4*. If
Logic Rule 2 is evaluated a s TRUE, the output
will go high. Otherwise, it will be low.
Logic Rule 3 [73]: See par. group 13-4*. If
Logic Rule 3 is evaluated a s TRUE, the output
will go high. Otherwise, it will be low.
SL digital output A [80]:Seepar.13-52
SL Controller Action. The input will go high
whenever the Smart Logic Action [38] "
Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [32]
"Set dig. out. A low" is e xecuted.
SL digital output B [81] :Seepar.13-52
SL Controller Action. The input will go high
whenever the Smart Logic Action [39] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [33]
"Set dig. out. A low" is executed.
SL digital output C [82]:Seepar.13-52
SL Controller Action. The input will go high
whenever the Smart Logic Action [40] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [34]
"Set dig. out. A low" is executed.
SL digital output D [83]:Seepar.13-52
SL Controller Action. The input will go high
whenever the Smart Logic Action [41] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [35]
"Set dig. out. A low" is executed.
SL digital output E [84]:Seepar.13-52
SL Controller Action. The input will go high
whenever the Smart Logic Action [42] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [36]
"Set dig. out. A low" is executed.
SL digital output F [85]:Seepar.13-52
SL Controller Action. The input will go high
whenever the Smart Logic Action [43] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [37]
"Set dig. out. A low" is executed.
Local ref. active [120]: The output will
be high if par. 3-13 Reference Site =[2]
"Local" or when par. 3-13 Re ference Site
=[0]"LinkedtoHand/Auto"atthesame
time the LCP is in Hand on mode.
Remote ref. active [121]: The output will
be high if par. 3-13 Reference Site =[
1]
"Remote" or when par. 3-13 Reference Site
= [0] Linked to Hand / Auto at the same
time the LCP is in Auto on mode.
No alarm [122]: T he output goes high
when no alarm is p resent.
Start cmd. active [123]:Theou
tput
goes high whenever there is an active Start
command (i.e. via digita l input bus connection
or [Hand on] or [Auto on], and
no Stop
or Start c ommand is active.
Running reverse [124]: The output is high
whenever the dri ve is run
ning counterclockwise
*
default setting ()display text []value for use in communication via serial communication port
170
MG.33.B
3.22 - VLT is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 Series and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals