FC 300 Design Guide
How to Program
• Brake ready, no fault [29]:Thebrakeis
ready for operation and there are no faults.
• Brake fault (IGBT) [30]: The output is Logic
"1" when the brake IGBT is short-circuited. Use
this function to protect the a djustable frequency
drive if there is a fault on the brake modules.
Use the output/ relay to cut out the line voltage
from the adjus table frequency drive.
• Relay 123 [31]: If Fieldbus profile [0]
is selected in par. 5-12, the relay is
activate. If OFF1, OFF2 or OFF3 (bit in
the control word) is Logic ’1’.
• Mech. brake control [32]:Enables
control of an external mechanical brake, see
description in the section Co ntrol of Mechanical
Brake,andpar. group2-2*
• Safe stop active [33]: Indicates that the safe
stop on terminal 37 has been activated.
• MCO controlled [51]
• Comparator 0 [60]: See par. group 13-1*. If
Comparator 0 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
• Comparator 1 [61]: See par. group 13-1*. If
Comparator 1 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
• Comparator 2 [62]: See par. group 13-1*. If
Comparator 2 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
• Comparator 3 [63]: See par. group 13-1*. If
Comparator 3 is evaluated as TRUE, the output
will go high. Otherwise, it will be low.
• Logic Rule 0 [70]: See par. group 13-4*. If
Logic Rule 0 is evaluated a s TRUE, the output
will go high. Otherwise, it will be low.
• Logic Rule 1 [71]: See par. group 13-4*. If
Logic Rule 1 is evaluated a s TRUE, the output
will go high. Otherwise, it will be low.
• Logic Rule 2 [72]: See par. group 13-4*. If
Logic Rule 2 is evaluated a s TRUE, the output
will go high. Otherwise, it will be low.
• Logic Rule 3 [73]: See par. group 13-4*. If
Logic Rule 3 is evaluated a s TRUE, the output
will go high. Otherwise, it will be low.
• SL digital output A [80]:Seepar.13-52
SL Controller Action. The input will go high
whenever the Smart Logic Action [38] "
Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [32]
"Set dig. out. A low" is e xecuted.
• SL digital output B [81] :Seepar.13-52
SL Controller Action. The input will go high
whenever the Smart Logic Action [39] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [33]
"Set dig. out. A low" is executed.
• SL digital output C [82]:Seepar.13-52
SL Controller Action. The input will go high
whenever the Smart Logic Action [40] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [34]
"Set dig. out. A low" is executed.
• SL digital output D [83]:Seepar.13-52
SL Controller Action. The input will go high
whenever the Smart Logic Action [41] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [35]
"Set dig. out. A low" is executed.
• SL digital output E [84]:Seepar.13-52
SL Controller Action. The input will go high
whenever the Smart Logic Action [42] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [36]
"Set dig. out. A low" is executed.
• SL digital output F [85]:Seepar.13-52
SL Controller Action. The input will go high
whenever the Smart Logic Action [43] "Set
dig. out. A high" is executed. The input will
go low whenever the Smart Logic Action [37]
"Set dig. out. A low" is executed.
• Local ref. active [120]: The output will
be high if par. 3-13 Reference Site =[2]
"Local" or when par. 3-13 Re ference Site
=[0]"LinkedtoHand/Auto"atthesame
time the LCP is in Hand on mode.
• Remote ref. active [121]: The output will
be high if par. 3-13 Reference Site =[
1]
"Remote" or when par. 3-13 Reference Site
= [0] Linked to Hand / Auto at the same
time the LCP is in Auto on mode.
• No alarm [122]: T he output goes high
when no alarm is p resent.
• Start cmd. active [123]:Theou
tput
goes high whenever there is an active Start
command (i.e. via digita l input bus connection
or [Hand on] or [Auto on], and
no Stop
or Start c ommand is active.
• Running reverse [124]: The output is high
whenever the dri ve is run
ning counterclockwise
*
default setting ()display text []value for use in communication via serial communication port
170
MG.33.B