Table 79: Wiring Configuration for Speed Up/Down
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
e30bu076.10
XD2.10
Parameter 5-10 Terminal 18 Digital Input
Parameter 5-12 Terminal 27 Digital Input
Parameter 5-13 Terminal 29 Digital Input
Parameter 5-14 Terminal 32 Digital Input
Notes/comments:
D IN 37 is an option.
Terminal 18 in the parameter title corresponds to terminal XD2.12 in the control compartment.
Terminal 27 in the parameter title corresponds to terminal XD2.14 in the control compartment.
Terminal 29 in the parameter title corresponds to terminal XD2.15 in the control compartment.
Terminal 32 in the parameter title corresponds to terminal XD2.16 in the control compartment.
Reference
Start (XD2.12)
Freeze ref (XD2.14)
Speed up (XD2.15)
Speed down (XD2.16)
Illustration 67: Speed Up/Down
AQ262139143212en-000301 / 130R0879 | 125Danfoss A/S © 2021.10
Wiring Configuration Examples
VLT® AutomationDrive FC 302
Operating Guide