Table 79: Wiring Configuration for Speed Up/Down
Parameters
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
e30bu076.10
XD2.10
XD2.11
XD2.12
XD2.13
XD2.18
XD2.14
XD2.15
XD2.16
XD2.17
XD2.19
Function
Setting
Parameter 5-10 Terminal 18 Digital Input
[8] Start*
Parameter 5-12 Terminal 27 Digital Input
[19] Freeze Reference
Parameter 5-13 Terminal 29 Digital Input
[21] Speed Up
Parameter 5-14 Terminal 32 Digital Input
[22] Speed Down
*=Deafult value
Notes/comments:
D IN 37 is an option.
Terminal 18 in the parameter title corresponds to terminal XD2.12 in the control compartment.
Terminal 27 in the parameter title corresponds to terminal XD2.14 in the control compartment.
Terminal 29 in the parameter title corresponds to terminal XD2.15 in the control compartment.
Terminal 32 in the parameter title corresponds to terminal XD2.16 in the control compartment.
e30bu077.10
Speed
Reference
Start (XD2.12)
Freeze ref (XD2.14)
Speed up (XD2.15)
Speed down (XD2.16)
Illustration 67: Speed Up/Down
AQ262139143212en-000301 / 130R0879 | 125Danfoss A/S © 2021.10
Wiring Configuration Examples
VLT® AutomationDrive FC 302
Operating Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals