EasyManuals Logo
Home>Danfoss>DC Drives>VLT AutomationDrive FC 302

Danfoss VLT AutomationDrive FC 302 User Manual

Danfoss VLT AutomationDrive FC 302
206 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #174 background imageLoading...
Page #174 background image
10.6.5 Digital Outputs
Programmable digital/pulse outputs
2
Terminal number
(1)
XD2.14, XD2.15
Voltage level at digital/frequency output
0–24 V
Maximum output current (sink or source)
40 mA
Maximum load at frequency output
1 kΩ
Maximum capacitive load at frequency output
10 nF
Minimum output frequency at frequency output
0 Hz
Maximum output frequency at frequency output
32 kHz
Accuracy of frequency output
Maximum error: 0.1% of full scale
Resolution of frequency outputs
12 bit
1
Can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
10.6.6 Digital Inputs
Programmable digital inputs
4 (6)
Terminal number
(1)
XD2.12, XD2.13, XD2.14, XD2.15, XD2.16, XD2.17
Logic
PNP or NPN
Voltage level
0–24 V DC
Voltage level, logic 0 PNP
<5 V DC
Voltage level, logic 1 PNP
>10 V DC
Voltage level, logic 0 NPN
(2)
>19 V DC
Voltage level, logic 1 NPN
(2)
<14 V DC
Maximum voltage on input
28 V DC
Pulse frequency range
0–110 kHz
(Duty cycle) minimum pulse width
4.5 ms
Input resistance, R
i
Approximately 4 kΩ
1
Terminals XD2.14 and XD2.15 can also be programmed as output.
2
Except STO input terminal XD2.19.
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
10.6.7 Pulse/Encoder Inputs
Programmable pulse/encoder inputs
2/1
Terminal number (pulse inputs)
XD2.15, XD2.17
Terminal number (encoder inputs)
(1)
XD2.16, XD2.17
Maximum frequency at terminals XD2.15, XD2.16, XD2.17 (push-
pull driven)
110 kHz
Maximum frequency at terminals XD2.15, XD2.16, XD2.17 (open
collector)
5 kHz
Maximum frequency at terminals XD2.15, XD2.16, XD2.17
4 kHz
Voltage level
See Control Input/Output and Control Data.
Maximum voltage on input
28 V DC
Input resistance, R
i
Approximately 4 kΩ
Pulse input accuracy (0.1–1 kHz)
Maximum error: 0.1% of full scale
AQ262139143212en-000301 / 130R0879174 | Danfoss A/S © 2021.10
Specifications
VLT® AutomationDrive FC 302
Operating Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals