Table 151: Power Losses for MCCB Option, 525–690 V
Model
525–550 V [W]
551–690 V [W]
NO
HO
NO
HO
N90K
11
7
10
7
N110
15
11
14
10
N132
23
15
21
14
N160
22
14
20
13
N200
32
22
29
20
N250
45
32
41
29
N315
61
45
56
41
N355
43
30
39
28
N400
53
36
49
33
N500
69
53
63
49
N560
77
69
77
63
N630
84
63
77
57
N710
114
84
104
77
11.6.5 Passive Harmonic Filter (PHF) Losses
Table 152: Power Losses for Passive Harmonic Filter Option, 380–500 V
Model
380–440 V [W]
441–500 V [W]
NO
HO
NO
HO
N90K
1083
841
1083
841
N110
1284
1083
1284
1083
N132
1511
1284
1511
1284
N160
1704
1511
1704
1511
N200
1814
1704
1814
1704
N250
2242
1814
1980
1814
N315
2302
2242
2242
1980
N355
2498
2302
2302
2242
N400
2613
2498
2498
2302
N450
2838
2613
2613
2498
N500
3160
2838
2838
2613
AQ262139143212en-000301 / 130R0879 | 201Danfoss A/S © 2021.10
Appendix
VLT® AutomationDrive FC 302
Operating Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals