10.10 Enclosure Airflow
225 mm (8.9 in)
e30bu132.10
1
2
225 mm (8.9 in)
Illustration 84: Enclosure Airflow in Sine-wave Filter, Passive Harmonic Filter, and Drive Cabinets (Side View)
Drive module cabinet
PHF and sine-wave cabinets
10.11 Fastener Torque Ratings
Apply the correct torque when tightening fasteners in the locations that are listed in the table. Too low or too high torque when
fastening an electrical connection results in a bad electrical connection. To ensure correct torque, use a torque wrench.
Table 137: Fastener Torque Ratings
Location
Bolt size
Torque [Nm (in-lb)]
Mains terminals
M10/M12
19 (168)/37 (335)
Motor terminals
M10/M12
19 (168)/37 (335)
Ground terminals
M8/M10
9.6 (84)/19.1 (169)
Brake terminals
M8
9.6 (84)
Relay terminals
0.5 (4)
Ground busbars between cabinets
M8
10 (88.5)
Brackets between cabinets
M6
8 (71)
Door/panel cover
M5
2.3 (20)
Cable entry plate
M5
2.3 (20)
Serial communication cover
M5
2.3 (20)
AQ262139143212en-000301 / 130R0879 | 189Danfoss A/S © 2021.10
Specifications
VLT® AutomationDrive FC 302
Operating Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals