4.11 Parameters: 12-** Ethernet
4.11.1 12-0* IP Settings
12-00 IP Address Assignment
Option: Function:
Select the IP address assignment
method.
[0] MANUAL IP address can be set in
parameter 12-01 IP Address IP
Address.
[1] DHCP IP address is assigned via DHCP
server.
[2] BOOTP IP address is assigned via BOOTP
server.
[10] * DCP DCP is assigned via the DCP
protocol.
[20] From node ID
12-01 IP Address
Range: Function:
0* [0 -
4294967295 ]
Congure the IP address of the
option. Read-only, if
parameter 12-00 IP Address
Assignment is set to DHCP or
BOOTP. In POWERLINK, the IP
address follows the
parameter 12-60 Node ID last byte
and the rst part is xed to
192.168.100 (node ID).
12-02 Subnet Mask
Range: Function:
0* [0 -
4294967295]
Congure the IP subnet mask of the
option. Read-only, if parameter 12-00 IP
Address Assignment is set to DHCP or
BOOTP. In POWERLINK, it is xed to
255.255.255.0.
12-03 Default Gateway
Range: Function:
0* [0 -
2147483647 ]
Congure the IP default gateway of
the option. Read-only, if
parameter 12-00 IP Address
Assignment is set to DHCP or
BOOTP. In a non-routed network,
this address is set to the IP address
of the IO Device.
12-04 DHCP Server
Range: Function:
0* [0 -
2147483647 ]
Read-only. Show the IP address of
the found DHCP or BOOTP server.
12-05 Lease Expires
Range: Function:
Size
related*
[ 0 - 0 ] Read-only. Show the lease time left
for the current DHCP-assigned IP
address.
12-06 Name Servers
Range: Function:
0* [0 -
2147483647 ]
IP addresses of domain name
servers. Can be automatically
assigned when using DHCP.
12-07 Domain Name
Range: Function:
0 [0 - 48 ] Domain name of the attached
network. Can be automatically
assigned when using DHCP
network.
12-08 Host Name
Range: Function:
0* [0 - 48 ] Logical (given) name of option.
NOTICE
The display of the frequency
converter only shows the rst
19 characters, but the
remaining characters are
stored in the frequency
converter. If hardware switches
are dierent from all ON or all
OFF, the switches have priority.
12-09 Physical Address
Range: Function:
0* [0 - 17 ] Read-only. Show the physical (MAC)
address of the option.
4.11.2 12-1* Ethernet Link Parameters
Apply to the whole parameter group.
Index [0] is used for port 1, and index [1] is used for port
2.
12-10 Link Status
Read-only. Shows the link status of the Ethernet ports.
Option: Function:
[0] * No Link
[1] Link
Parameter Descriptions VLT® AutomationDrive FC 361
112 Danfoss A/S © 03/2019 All rights reserved. MG06J202
44

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 361

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 361 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 361 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 361
CategoryDC Drives
LanguageEnglish

Related product manuals