EasyManuals Logo
Home>Danfoss>DC Drives>VLT AutomationDrive FC 361

Danfoss VLT AutomationDrive FC 361 Programming Guide

Danfoss VLT AutomationDrive FC 361
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #63 background imageLoading...
Page #63 background image
3-95 Ramp Delay
Range: Function:
Size
related*
[ 0 - 0] Enter the delay required from
activation of the digital potenti-
ometer function until the frequency
converter starts to ramp the
reference. With a delay of 0 ms, the
reference starts to ramp when
increase/decrease is activated. See
also parameter 3-91 Ramp Time.
4.5 Parameters: 4-** Limits/Warnings
4.5.1 4-1* Motor Limits
Dene torque, current, and speed limits for the motor, and
the reaction of the frequency converter when the limits are
exceeded.
A limit may generate a message in the display. A warning
always generates a message in the display or on the
eldbus. A monitoring function may initiate a warning or a
trip, after which the frequency converter stops and
generates an alarm message.
4-10 Motor Speed Direction
Option: Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
Select the motor speed direction(s)
required. Use this parameter to
prevent unwanted reversing. When
parameter 1-00 Conguration Mode
is set to [3] Process,
parameter 4-10 Motor Speed
Direction is set to [0] Clockwise as
default. The setting in
parameter 4-10 Motor Speed
Direction does not limit options for
setting parameter 4-13 Motor Speed
High Limit [RPM].
[0] Clockwise The reference is set to CW rotation.
Reversing input (default terminal
19) must be open.
[1] Counter
clockwise
The reference is set to CCW
rotation. Reversing input (default
terminal 19) must be closed. If
reversing is required with reverse
input open, the motor direction can
be changed by
parameter 1-06 Clockwise Direction.
[2] Both
directions
Allows the motor to rotate in both
directions.
4-11 Motor Speed Low Limit [RPM]
Range: Function:
Size
related*
[ 0 - par. 4-13
RPM]
Enter the minimum limit for motor
speed. The motor speed low limit
can be set to correspond to the
manufacturers recommended
minimum motor speed. The motor
speed low limit must not exceed
the setting in parameter 4-13 Motor
Speed High Limit [RPM].
4-12 Motor Speed Low Limit [Hz]
Range: Function:
Size
related*
[ 0 - par. 4-14
Hz]
Enter the minimum limit for motor
speed. The motor speed low limit
can be set to correspond to the
minimum output frequency of the
motor shaft. The motor speed low
limit must not exceed the setting in
parameter 4-14 Motor Speed High
Limit [Hz].
4-13 Motor Speed High Limit [RPM]
Range: Function:
Size
related*
[ par. 4-11 -
60000 RPM]
Enter the maximum limit for motor
speed. The motor speed high limit
can be set to correspond to the
manufacturers maximum nominal
motor speed. The motor speed high
limit must exceed the setting in
parameter 4-11 Motor Speed Low
Limit [RPM].
4-14 Motor Speed High Limit [Hz]
Range: Function:
Size
related*
[ par. 4-12 -
par. 4-19 Hz]
Enter the maximum limit for motor
speed in Hz. Parameter 4-14 Motor
Speed High Limit [Hz] can be set to
correspond to the manufacturer's
recommended maximum motor
speed. The motor speed high limit
must exceed the value in
parameter 4-12 Motor Speed Low
Limit [Hz]. The output frequency
must not exceed 10% of the
switching frequency
(parameter 14-01 Switching
Frequency).
4-16 Torque Limit Motor Mode
Range: Function:
Size
related*
Application
dependent
*
[ 0 -
1000.0 %]
[Application
dependent]
This function limits the torque on
the shaft to protect the mechanical
installation.
Parameter Descriptions Programming Guide
MG06J202 Danfoss A/S © 03/2019 All rights reserved. 61
4 4

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 361

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 361 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 361 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 361
CategoryDC Drives
LanguageEnglish

Related product manuals