4.19.3 22-6* Broken-belt Detection
Use broken-belt detection in both closed-loop systems and
open-loop systems for pumps and fans. If the estimated
motor torque (current) is below the broken-belt torque
(current) value (parameter 22-61 Broken Belt Torque), the
frequency converter output frequency is above or equal to
15 Hz, and the condition has been active for
parameter 22-62 Broken Belt Delay, parameter 22-60 Broken
Belt Function is performed.
22-60 Broken Belt Function
Option: Function:
Select the actions to be performed
if the broken-belt condition is
detected.
[0] * O
[1] Warning The frequency converter continues
to run, but activates warning 95,
Broken belt. A frequency converter
digital output or a serial communi-
cation bus communicates a warning
to other equipment.
[2] Trip The frequency converter stops
running and activates alarm 95,
Broken belt. A frequency converter
digital output or a serial communi-
cation bus communicates an alarm
to other equipment.
[3] Stop and Trip
22-61 Broken Belt Torque
Range: Function:
10 %* [0 - 100 %] Set the broken-belt torque as a
percentage of the rated motor
torque.
22-62 Broken Belt Delay
Range: Function:
10 s* [0 - 600 s] Set the time for which the broken-
belt conditions must be active
before carrying out the action
selected in parameter 22-60 Broken
Belt Function.
4.20 Parameters: 30-** Special Features
4.20.1 30-2* Adv. Start Adjust
30-20 High Starting Torque Time [s]
Range: Function:
Size
related*
[0 - 60 s] This function is active together with
speed control closed loop. In order
to obtain a high starting torque,
approximately 2 x I
VLT,N
for
30-20 High Starting Torque Time [s]
Range: Function:
maximum 0.5 s. However, the
current is limited by the protection
limit of the frequency converter.
30-21 High Starting Torque Current [%]
Range: Function:
Size
related*
[ 0 - 200.0 %] High starting torque current for PM
motor in VVC
+
mode without
feedback.
30-22 Locked Rotor Protection
Option: Function:
Available for PM motors only, in
VVC
+
open-loop mode.
[0] O
[1] On Protects the motor from the locked
rotor condition. The control
algorithm detects a possible locked
rotor condition in the motor and
trips the frequency converter to
protect the motor.
30-23 Locked Rotor Detection Time [s]
Range: Function:
Size
related*
[0.05 - 1 s] Time period for detecting the
locked rotor condition. A low
parameter value leads to faster
detection.
30-24 Locked Rotor Detection Speed Error [%]
Range: Function:
25 %* [0 - 100 %]
4.21 Parameters: 40-** Special Settings
40-40 Fault Log: Ext. Reference
Range: Function:
0 %* [-200 -
200 %]
View the present reference value
applied on impulse or analog basis,
when the logged event occurred.
40-41 Fault Log: Frequency
Range: Function:
0 Hz* [0 - 6500 Hz] View the actual motor frequency
value, when the logged event
occurred.
40-42 Fault Log: Current
Range: Function:
0 A* [0 - 10000 A] View the motor current measured
when the logged event occurred.
Parameter Descriptions Programming Guide
MG06J202 Danfoss A/S © 03/2019 All rights reserved. 157
4 4

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 361

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 361 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 361 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 361
CategoryDC Drives
LanguageEnglish

Related product manuals