13-52 SL Controller Action
Option: Function:
[29] Start timer 0 Starts timer 0, see
parameter 13-20 SL Controller Timer
for further description.
[30] Start timer 1 Starts timer 1, see
parameter 13-20 SL Controller Timer
for further description.
[31] Start timer 2 Starts timer 2, see
parameter 13-20 SL Controller Timer
for further description.
[32] Set digital out
A low
Any output with smart logic output
A is low.
[33] Set digital out
B low
Any output with smart logic output
B is low.
[34] Set digital out
C low
Any output with smart logic output
C is low.
[35] Set digital out
D low
Any output with smart logic output
D is low.
[36] Set digital out
E low
Any output with smart logic output
E is low.
[37] Set digital out
F low
Any output with smart logic output
F is low.
[38] Set digital out
A high
Any output with smart logic output
A is high.
[39] Set digital out
B high
Any output with smart logic output
B is high.
[40] Set digital out
C high
Any output with smart logic output
C is high.
[41] Set digital out
D high
Any output with smart logic output
D is high.
[42] Set digital out
E high
Any output with smart logic output
E is high.
[43] Set digital out
F high
Any output with smart logic output
F is high.
[60] Reset Counter
A
Resets counter A to 0.
[61] Reset Counter
B
Resets counter B to 0.
[70] Start timer 3 Starts timer 3, see
parameter 13-20 SL Controller Timer
for further description.
[71] Start timer 4 Starts timer 4, see
parameter 13-20 SL Controller Timer
for further description.
[72] Start timer 5 Starts timer 5, see
parameter 13-20 SL Controller Timer
for further description.
13-52 SL Controller Action
Option: Function:
[73] Start timer 6 Starts timer 6, see
parameter 13-20 SL Controller Timer
for further description.
[74] Start timer 7 Starts timer 7, see
parameter 13-20 SL Controller Timer
for further description.
[80] Sleep Mode
4.13 Parameters: 14-** Special Functions
14-00 Switching Pattern
Option: Function:
Select the switching pattern: 60°
AVM or SFAVM.
NOTICE
The frequency converter may
adjust the switching pattern
automatically to avoid a trip.
[0] 60 AVM
[1] * SFAVM
14-01 Switching Frequency
Select the frequency converter switching frequency. Changing
the switching frequency reduces acoustic noise from the motor.
Default values depend on power size.
Option: Function:
NOTICE
The output frequency value of
the frequency converter must
never exceed 10% of the
switching frequency. When the
motor is running, adjust the
switching frequency in
parameter 14-01 Switching
Frequency to minimize motor
noise.
NOTICE
To avoid a trip, the frequency
converter can adjust the
switching frequency automat-
ically.
[0] 1.0 kHz
[1] 1.5 kHz
[2] 2.0 kHz
[3] 2.5 kHz
[4] 3.0 kHz
[5] 3.5 kHz
[6] 4.0 kHz
[7] 5.0 kHz
Parameter Descriptions Programming Guide