13-52 SL Controller Action
Option: Function:
[29] Start timer 0 Starts timer 0, see
parameter 13-20 SL Controller Timer
for further description.
[30] Start timer 1 Starts timer 1, see
parameter 13-20 SL Controller Timer
for further description.
[31] Start timer 2 Starts timer 2, see
parameter 13-20 SL Controller Timer
for further description.
[32] Set digital out
A low
Any output with smart logic output
A is low.
[33] Set digital out
B low
Any output with smart logic output
B is low.
[34] Set digital out
C low
Any output with smart logic output
C is low.
[35] Set digital out
D low
Any output with smart logic output
D is low.
[36] Set digital out
E low
Any output with smart logic output
E is low.
[37] Set digital out
F low
Any output with smart logic output
F is low.
[38] Set digital out
A high
Any output with smart logic output
A is high.
[39] Set digital out
B high
Any output with smart logic output
B is high.
[40] Set digital out
C high
Any output with smart logic output
C is high.
[41] Set digital out
D high
Any output with smart logic output
D is high.
[42] Set digital out
E high
Any output with smart logic output
E is high.
[43] Set digital out
F high
Any output with smart logic output
F is high.
[60] Reset Counter
A
Resets counter A to 0.
[61] Reset Counter
B
Resets counter B to 0.
[70] Start timer 3 Starts timer 3, see
parameter 13-20 SL Controller Timer
for further description.
[71] Start timer 4 Starts timer 4, see
parameter 13-20 SL Controller Timer
for further description.
[72] Start timer 5 Starts timer 5, see
parameter 13-20 SL Controller Timer
for further description.
13-52 SL Controller Action
Option: Function:
[73] Start timer 6 Starts timer 6, see
parameter 13-20 SL Controller Timer
for further description.
[74] Start timer 7 Starts timer 7, see
parameter 13-20 SL Controller Timer
for further description.
[80] Sleep Mode
4.13 Parameters: 14-** Special Functions
14-00 Switching Pattern
Option: Function:
Select the switching pattern: 60°
AVM or SFAVM.
NOTICE
The frequency converter may
adjust the switching pattern
automatically to avoid a trip.
[0] 60 AVM
[1] * SFAVM
14-01 Switching Frequency
Select the frequency converter switching frequency. Changing
the switching frequency reduces acoustic noise from the motor.
Default values depend on power size.
Option: Function:
NOTICE
The output frequency value of
the frequency converter must
never exceed 10% of the
switching frequency. When the
motor is running, adjust the
switching frequency in
parameter 14-01 Switching
Frequency to minimize motor
noise.
NOTICE
To avoid a trip, the frequency
converter can adjust the
switching frequency automat-
ically.
[0] 1.0 kHz
[1] 1.5 kHz
[2] 2.0 kHz
[3] 2.5 kHz
[4] 3.0 kHz
[5] 3.5 kHz
[6] 4.0 kHz
[7] 5.0 kHz
Parameter Descriptions Programming Guide
MG06J202 Danfoss A/S © 03/2019 All rights reserved. 127
4 4

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 361

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 361 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 361 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 361
CategoryDC Drives
LanguageEnglish

Related product manuals