3.1.7 Initial Commissioning
The easiest way of carrying out the initial commissioning is by pressing [Quick Menu] and following the quick set-up
procedure using LCP 102 (read Table 3.3 from left to right). The example applies to open-loop applications.
Press
Q2 Quick Menu.
Parameter 0-01 Language
Set language.
Parameter 1-20 Motor Power [kW]
Set motor nameplate power.
Parameter 1-22 Motor Voltage
Set nameplate voltage.
Parameter 1-23 Motor Frequency
Set nameplate frequency.
Parameter 1-24 Motor Current
Set nameplate current.
Parameter 1-25 Motor Nominal Speed
Set nameplate speed in RPM.
Parameter 5-12 Terminal 27 Digital
Input
If terminal default is [2] Coast
inverse, it is possible to change
this setting to [0] No function.
No connection to terminal 27 is
then needed for running AMA.
Parameter 1-29 Automatic Motor
Adaptation (AMA)
Set desired AMA function.
Enable complete AMA is
recommended.
Parameter 3-02 Minimum Reference
Set the minimum speed of the
motor shaft.
Parameter 3-03 Maximum Reference
Set the maximum speed of the
motor shaft.
Parameter 3-41 Ramp 1 Ramp Up Time
Set the ramp-up time with
reference to synchronous motor
speed, n
s
.
Parameter 3-42 Ramp 1 Ramp Down
Time
Set the ramp-down time with
reference to synchronous motor
speed, n
s
.
Parameter 3-13 Reference Site
Set the site from where the
reference must work.
Table 3.3 Quick Set-up Procedure
Programming VLT® AutomationDrive FC 361
18 Danfoss A/S © 03/2019 All rights reserved. MG06J202