13-52 SL Controller Action
Option: Function:
Select the action corresponding to
the SLC event. Actions are executed
when the corresponding event
(dened in parameter 13-51 SL
Controller Event) is evaluated as
true.
[0] DISABLED
[1] No action
[2] Select set-up 1 Changes the active set-up
(parameter 0-10 Active Set-up) to 1.
If the set-up is changed, it merges
with other set-up commands
coming from either the digital
inputs or via a eldbus.
[3] Select set-up 2 Changes the active set-up
(parameter 0-10 Active Set-up) to 2.
If the set-up is changed, it merges
with other set-up commands
coming from either the digital
inputs or via a eldbus.
[4] Select set-up 3 Changes the active set-up
(parameter 0-10 Active Set-up) to 3.
If the set-up is changed, it merges
with other set-up commands
coming from either the digital
inputs or via a eldbus.
[5] Select set-up 4 Changes the active set-up
(parameter 0-10 Active Set-up) to 4.
If the set-up is changed, it merges
with other set-up commands
coming from either the digital
inputs or via a eldbus.
[10] Select preset
ref 0
Selects preset reference 0.
If the active preset reference is
changed, it merges with other
preset reference commands coming
from either the digital inputs or via
a eldbus.
[11] Select preset
ref 1
Selects preset reference 1.
If the active preset reference is
changed, it merges with other
preset reference commands coming
from either the digital inputs or via
a eldbus.
[12] Select preset
ref 2
Selects preset reference 2.
If the active preset reference is
changed, it merges with other
preset reference commands coming
from either the digital inputs or via
a eldbus.
[13] Select preset
ref 3
Selects preset reference 3.
13-52 SL Controller Action
Option: Function:
If the active preset reference is
changed, it merges with other
preset reference commands coming
from either the digital inputs or via
a eldbus.
[14] Select preset
ref 4
Selects preset reference 4.
If the active preset reference is
changed, it merges with other
preset reference commands coming
from either the digital inputs or via
a eldbus.
[15] Select preset
ref 5
Selects preset reference 5.
If the active preset reference is
changed, it merges with other
preset reference commands coming
from either the digital inputs or via
a eldbus.
[16] Select preset
ref 6
Selects preset reference 6.
If the active preset reference is
changed, it merges with other
preset reference commands coming
from either the digital inputs or via
a eldbus.
[17] Select preset
ref 7
Selects preset reference 7.
If the active preset reference is
changed, it merges with other
preset reference commands coming
from either the digital inputs or via
a eldbus.
[18] Select ramp 1 Selects ramp 1.
[19] Select ramp 2 Selects ramp 2.
[20] Select ramp 3 Selects ramp 3.
[21] Select ramp 4 Selects ramp 4.
[22] Run Issues a start command to the
frequency converter.
[23] Run reverse Issues a start reverse command to
the frequency converter.
[24] Stop Issues a stop command to the
frequency converter.
[25] Qstop Issues a quick stop command to
the frequency converter.
[26] Dcstop Issues a DC stop command to the
frequency converter.
[27] Coast The frequency converter coasts
immediately. All stop commands
including the coast command stop
the SLC.
[28] Freeze output Freezes the output frequency of the
frequency converter.