NOTICE
Changing parameter 4-16 Torque Limit Motor Mode when
parameter 1-00 Conguration Mode is set to [0] Speed
open loop, parameter 1-66 Min. Current at Low Speed is
automatically readjusted.
NOTICE
The torque limit reacts to the actual, non-ltered torque,
including torque spikes. This is not the torque that is
seen from the LCP or the eldbus as that torque is
ltered.
4-17 Torque Limit Generator Mode
Range: Function:
100 %* [ 0 -
1000.0 %]
This function limits the torque on
the shaft to protect the mechanical
installation.
4-18 Current Limit
Range: Function:
Size
related*
[ 1.0 -
1000.0 %]
NOTICE
If [20] ATEX ETR is selected in
parameter 1-90 Motor Thermal
Protection, set
parameter 4-18 Current Limit
current limit to 150%.
This is a true current limit function
that continues in the oversyn-
chronous range. However, due to
eld weakening the motor torque
at current limit will drop
accordingly when the voltage
increase stops above the
synchronized speed of the motor.
4-19 Max Output Frequency
Range: Function:
Size
related*
[ 1 - 590 Hz]
NOTICE
This parameter cannot be
adjusted while the motor is
running.
NOTICE
Maximum output frequency
cannot exceed 10% of the
inverter switching frequency
(parameter 14-01 Switching
Frequency).
Provides a nal limit on the output
frequency for improved safety in
applications where overspeeding is
to be avoided. This limit is nal in
4-19 Max Output Frequency
Range: Function:
all congurations (independent of
the setting in
parameter 1-00 Conguration Mode).
4.5.2 4-2* Limit Factors
4-20 Torque Limit Factor Source
Option: Function:
Select an analog input for scaling
the settings in
parameter 4-16 Torque Limit Motor
Mode and parameter 4-17 Torque
Limit Generator Mode 0–100% (or
inverse). The signal levels
corresponding to 0% and 100% are
dened in the analog input scaling,
for example parameter group 6-1*
Analog Input 1. This parameter is
only active when
parameter 1-00 Conguration Mode
is in Speed Open Loop or Speed
Closed Loop.
[0] * No function
[2] Analog in 53
[4] Analog in 53
inv
[6] Analog in 54
[8] Analog in 54
inv
[10] Analog in
X30-11
[12] Analog in
X30-11 inv
[14] Analog in
X30-12
[16] Analog in
X30-12 inv
4-21 Speed Limit Factor Source
Option: Function:
Select an analog input for scaling
the settings in parameter 4-19 Max
Output Frequency 0–100% (or the
other way around). The signal levels
corresponding to 0% and 100% are
dened in the analog input scaling,
for example parameter group 6-1*
Analog Input 1. This parameter is
only active when
parameter 1-00 Conguration Mode
is in [4] Torque Open Loop.
[0] * No function
Parameter Descriptions VLT® AutomationDrive FC 361
62 Danfoss A/S © 03/2019 All rights reserved. MG06J202
44

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 361

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 361 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 361 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 361
CategoryDC Drives
LanguageEnglish

Related product manuals