130BA069.10
Time
RPM
P 4-13 RPM
high limit
Reference
P 1-25
Motor speed
low limit
P 4-11 RPM
P 3-81
Qramp
Qstop
Illustration 4.21 Quick Stop Ramp Time
3-82 Starting Ramp Up Time
Range: Function:
Size
related*
[0.01 - 3600
s]
The ramp-up time is the
acceleration time from 0 rpm to the
nominal motor speed set in
parameter 1-25 Motor Nominal Speed
when high starting torque is active.
4.4.8 3-9* Digital Pot.Meter
The digital potentiometer enables increase or decrease of
the actual reference by adjusting the set-up of the digital
inputs using the functions increase, decrease, or clear. To
activate the function, set at least 1 digital input to increase
or decrease.
Speed
Time (s)
Inc
130BA158.11
P 3-95
Illustration 4.22 Increase Actual Reference
Speed
Time (s)
Dec
Inc
130BA159.11
P 3-95
Illustration 4.23 Increase/Decrease Actual Reference
3-90 Step Size
Range: Function:
0.10 %* [0.01 -
200 %]
Enter the increment size required
for increase/decrease as a
percentage of the synchronous
motor speed, n
s
. If increase/
decrease is activated, the resulting
reference is increased or decreased
by the value set in this parameter.
3-91 Ramp Time
Range: Function:
1 s* [0 - 3600 s] Enter the ramp time, that is the
time for adjustment of the
reference 0–100% of the specied
digital potentiometer function
(increase, decrease, or clear).
If increase/decrease is activated for
longer than the ramp delay period
specied in parameter 3-95 Ramp
Delay, the actual reference is
ramped up/down according to this
ramp time. The ramp time is
dened as the time used to adjust
the reference by the step size
specied in parameter 3-90 Step
Size.
3-92 Power Restore
Option: Function:
[0] * O Resets the digital potentiometer
reference to 0% after power-up.
[1] On Restores the most recent digital
potentiometer reference at power-
up.
3-93 Maximum Limit
Range: Function:
100 %* [-200 -
200 %]
Set the maximum allowed value for
the resulting reference. This is
recommended if the digital potenti-
ometer is used for ne-tuning of
the resulting reference.
3-94 Minimum Limit
Range: Function:
-100 %* [-200 -
200 %]
Set the minimum allowed value for
the resulting reference. This is
recommended if the digital potenti-
ometer is used for ne-tuning of
the resulting reference.
Parameter Descriptions VLT® AutomationDrive FC 361
60 Danfoss A/S © 03/2019 All rights reserved. MG06J202
44

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 361

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 361 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 361 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 361
CategoryDC Drives
LanguageEnglish

Related product manuals