14-10 Mains Failure
Option: Function:
the relatively high level on the DC-
link during ramp down.
14-11*1.35
Ref
790 V
0
A B C D
130BC920.10
U
n [RPM]
t [S]
DC
U
DC
[V]
t [S]
A Normal operation
B Mains failure
C Kinetic back-up
D Trip
Illustration 4.41 Kinetic Back-up
Trip
[6] Alarm
[7] Kin. back-up,
trip w
recovery
This option is valid in VVC
+
only.
Kinetic back-up with recovery
combines the features of kinetic
back-up and kinetic back-up with
trip. This feature makes it possible
to select between kinetic back-up
and kinetic back-up with trip, based
on a recovery speed, congurable
in parameter 14-15 Kin. Back-up Trip
Recovery Level. If mains does not
return, the frequency converter
ramps down to 0 RPM and trips. If
mains returns while in kinetic back-
up at a speed above the value in
parameter 14-15 Kin. Back-up Trip
Recovery Level, normal operation is
resumed. This is equal to [4] Kinetic
Back-up. The DC level during [7]
Kinetic back-up is
parameter 14-11 Mains Fault Voltage
Level x 1.35.
14-10 Mains Failure
Option: Function:
Ref
U
DC
14-15
A B C D EA
130BC922.10
U
DC
[V]
n [RPM]
t [S]
t [S]
14-11*1.35
A Normal operation
B Mains failure
C Kinetic back-up
D Mains return
E Normal operation: ramping
Illustration 4.42 Kinetic Back-Up,
Trip with Recovery where Mains
Returns above
Parameter 14-15 Kin. Back-up Trip
Recovery Level
If mains return while in kinetic
back-up at a speed below
parameter 14-15 Kin. Back-up Trip
Recovery Level, the frequency
converter ramps down to 0 RPM
using the ramp and then trips. If
the ramp is slower than the system
ramping down on its own, the
ramping is done mechanically and
U
DC
is at the normal level (U
DC, m
x
1.35).
14-11*1.35
Ref
U
DC
A B C D E F
130BC923.10
0
U
DC
[V]
n [RPM]
t [S]
t [S]
A Normal operation
B Mains failure
C Kinetic back-up
D Mains return
E Kinetic back-up, ramping to trip
F Trip
Illustration 4.43 Kinetic Back-Up,
Trip with Recovery, Trip Slow
Ramp where Mains Returns
below Parameter 14-15 Kin. Back-
up Trip Recovery Level, in this
Illustration a Slow Ramp is Used
Parameter Descriptions VLT® AutomationDrive FC 361
130 Danfoss A/S © 03/2019 All rights reserved. MG06J202
44

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 361

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 361 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 361 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 361
CategoryDC Drives
LanguageEnglish

Related product manuals