AS Series Module Manual
8- 6
CR# Name Description
Att.
Default
7
weight measured exceeds the limit, an
alarm is triggered. The value should be
greater than 1.
8 Filter mode for CH1
0: no filter (default)
1: maximum filter mode
2: average filter mode
R/W
0
9 Maximum filter for CH1
Range: 0–8; the bigger the number the
stronger the filter
R/W
1
10
Average weight measured
times for CH1
Range: 1–100
(for FW V1.04: 1–400 is available)
R/W
10
11
Upper limit of the zero return
for CH1
Floating-point format
Determines the current weight as the zero
point in the upper/lower range; when the
lower range is larger than the upper range,
the lower range is read as the upper range
and vice versa.
R/W
10
12
13
Lower limit of the zero return
for CH1
R/W
-10
14
15
Zero point tracking time for
CH1
Range: 5–500
Unit: 100 ms
R/W
10
16
Zero point tracking range for
CH1
Floating-point format
Range: 0–10000; 0: disabled
R/W
0
17
18 Calibration points for CH1 Range: 2–20
R/W
2
19–58 Calibrated weight for CH1
Floating-point format
Calibrated weight of the calibration points
1–20
R/W
-
59 Display options for CH2
0: disabled
1: gross weight
2: net weight
3: raw data
R/W
1
60 Eigenvalue for CH2
0:1 mV/V
1:2 mV/V
2:4 mV/V
R/W
1