Chapter 11 DeviceNet Master Scanner Module AS01DNET-A
11-3
1
1
11.1 Introduction of AS01DNET-A
Thank you for choosing Delta AS01DNET-A. Please read this chapter carefully before use so as to ensure correct
installation and operation of AS01DNET-A.
The instruction is simply a guideline for operation of the product and the details on the DeviceNet protocol is
excluded here. Please refer to relevant articles and literatures for more details on the DeviceNet protocol.
AS01DNET-A, a DeviceNet network module can work in two modes: master /slave and RTU. The RTU-
Master/Slave switch is used for selecting one of the two modes. When AS01DNET-A works in master/slave mode,
it makes up the DeviceNet master or slave with AS-series PLC together. When working in RTU mode, AS01DNET-
A needs an external 24VDC power supply and can connect AS-series I/O modules onits right side.
Refer to Section 11.4 and 11.5 for details about master/slave mode and RTU mode.
11.1.1 Feature
Supports the Group 2 server slave and Group 2 only servers.
Supports the explicit connection in the predefined master/slave connection and I/O polling connection.
Able to work as a DeviceNet master or slave as well as a remote RTU connecting AS series I/O modules.
The network configuration software DeviceNet Builder offers the graphical configuration interface.
Supports the EDS file configuration in the DeviceNet network configruation tool.
11.1.2 Specifications
DeviceNet Connector
Item Specifications
Transmission method
CAN
Electrical isolation
DC500V
Connector type
Removable terminal block with screws (5.08mm)
Communication cable
2 communication wires, 2 power wires and 1 shielded wire included.
DeviceNet Communication
Item Specifications
Message type
I/O polling connection, explicit connection
Baud rate
Standard: 125 kbps, 250 kbps and 500 kbps
Extension: 10 kbps, 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps,
800kbps and 1M bps.
Electrical Specification
Item Specifications
Voltage
The power wires of the communication cable provide 11 ~ 25 VDC.
Current
28mA (typical value), 125mA impulse current (24 VDC)