Chapter 5 Trial operation and Tuning ASDA-A2
5-6 Revision February, 2017
5.3 JOG Trial Run without Load
It is very convenient to test the motor and servo drive with the method of JOG trial run without load
since the extra wiring is unnecessary. For safety reasons, it is recommended to set JOG at low
speed. Please see the following descriptions.
Step 1: Use software setting to Servo ON. Set parameter P2-30 to 1. This setting is to force the
servo ON through software.
Step 2: Set P4-05 as JOG speed (Unit: r/min). After setting the desired JOG speed, press the SET
Key, the servo drive will enter JOG mode.
Step 3: Press the MODE Key to exist JOG mode.