Chapter 11 Summary of Parameter SettingsME300
11-35
10 Speed Feedback Control Parameters
Pr. Explanation Settings Default
10-16 Pulse input type setting
0: Disabled
5: Single-phase input
6: PWM signal input
0
10-29
Top limit of frequency
deviation
0.00–100.00 Hz 20.00
10-31
I/F mode, current
command
0–150% rated current of the motor 40
10-32
PM FOC sensorless
speed estimator
bandwidth
0.00–600.00 Hz 5.00
10-34
PM sensorless speed
estimator low-pass filter
gain
0.00–655.35 1.00
10-42
Initial angle detection
pulse value
0.0–3.0 1.0
10-49
Zero voltage time during
start-up
00.000–60.000 sec. 00.000
10-51 Injection frequency 0–1200 Hz 500
10-52 Injection magnitude 0.0–200.0 V
15.0/
30.0
10-53 Position detection method
0: Disabled
1:
Internal 1/4 rated current attracting the rotor to zero
degrees
2: High frequency injection
3: Pulse injection
0