Chapter 12 Description of Parameter SettingsME300
12.1-09-12
Communication Main Frequency
Default: 60.00
Settings 0.00–599.00 Hz
When you set Pr.00-20 to 1 (RS-485 serial communication), the AC motor drive saves the last
Frequency command into Pr.09-10 when there is abnormal power off or momentary power loss.
After the drive reboots when power is restored, it checks the frequency in Pr.09-10 if no new
Frequency command is input. When a Frequency command of 485 changes (the Frequency
command source must be set as Modbus), this parameter also changes.
Block Transfer 1
Block Transfer 2
Block Transfer 3
Block Transfer 4
Block Transfer 5
Block Transfer 6
Block Transfer 7
Block Transfer 8
Block Transfer 9
Block Transfer 10
Block Transfer 11
Block Transfer 12
Block Transfer 13
Block Transfer 14
Block Transfer 15
Block Transfer 16
Default: 0
Settings 0–65535
There is a group of block transfer parameters available in the AC motor drive (Pr.09-11–Pr.09-26).
Using communication code 03H, you can store the parameters (Pr.09-11–Pr.09-26) that you want
to read.
Communication Decoding Method
Default: 1
Settings 0: Decoding method 1
1: Decoding method 2
Decoding Method 1 Decoding Method 2
Source of
Operation
Control
Digital Keypad Digital keypad controls the drive action regardless of decoding method 1 or 2.
External Terminal External terminal controls the drive action regardless of decoding method 1 or 2.
RS-485 Refer to address: 2000h–20FFh Refer to address: 6000h–60FFh