Chapter 12 Description of Parameter SettingsME300
12.1-02-21
EF Active when the Terminal Count Value Reached
Default: 0
Settings 0: Terminal count value reached, no EF displays (continues to operate).
1: Terminal count value reached, EF is active.
Initial Frequency Command (F) Mode after Stop
Default: 0
Settings 0: Use current Frequency command
1: Use zero Frequency command
2: Refer to Pr.02-83 to set up
Initial Frequency Command (F) Setting after Stop
Default: 60.00
Settings 0.00–599.0 Hz