Chapter 12 Description of Parameter SettingsME300
12.1-03-16
AVI Terminal Input Selection
Default: 0
Settings
0: 0–10 V
1: 0–20 mA (Pr.03-57–03-62 is valid)
2: 4–20 mA (Pr.03-57–03-62 is valid)
Switch between voltage mode and current mode must work with manual switch. Refer to Chapter
06 for more information on AVI terminals.
AFM DC Output Setting Level
Default: 0.00
Settings
0.00–100.00%
AFM Filter Output Time
Default: 0.01
Settings
0.00–20.00 sec.
VR Input Selection
Default: 1
Settings 0: Disable
1: Frequency command
VR Input Bias
Default: 0.0
Settings
-100.0–100.0%
VR Positive / Negative Bias
Default: 0
Settings
0: No bias
1: Lower than or equal to
bias
2: Greater than or equal to bias
3:
The absolute value of the bias voltage while serving as the center
4: Bias serves as the center
VR Gain
Default: 100.0
Settings
-500.0–500.0%
VR Filter Time
Default: 0.01
Settings 0–2.00 sec.