Minimum Mounting Clearance and Installation
Prevent fiber particles, scraps of paper, shredded wood, sawdust, metal particles, etc. from adhering
to the heat sink.
Install the AC motor drive in a metal cabinet. When installing one drive below another one, use a
metal separator between the AC motor drives to prevent mutual heating and to prevent the risk of
accidental fire.
Install the AC motor drive in Pollution Degree 2 environments only, where normally only non-
conductive pollution occurs and temporary conductivity caused by condensation is expected.
Mount the drive in an IP54 cabinet in order to maintain the Pollution Degree 2 or in a pollution-
controlled environment.
The following figures are for reference only.
Airflow direction: inflow outflow distance
Single drive installation Side-by-side horizontal installation /
Zero stack installation
Minimum mounting clearance
Installation method A (mm) B (mm) C (mm)
Ambient temperature (
o
C)
Max.
(Without derating)
Max.
(derating)
Single drive installation
50 30 - 50 60
Side-by-side horizontal installation
50 30 30 50 60
Zero stack installation
50 30 0 40 50
NOTE
The minimum mounting clearances A–C in the table above apply to AC motor drives installation. Failing to follow the
minimum mounting clearances may cause the fan to malfunction and heat dissipation problems may occur.