Chapter 12 Description of Parameter SettingsME300
12.1-02-9
When Pr.11-00 bit 7=1, the frequency is not saved. The Frequency command returns to zero
when the drive stops, and the displayed frequency is 0.00 Hz. At this time, the increasing or
decreasing frequency command (F) by using the UP or DOWN key is valid only when the drive is
running.
When Pr.02-09 is set to 0: the increasing or decreasing frequency command (F) operates
according to the setting for acceleration or deceleration time (refer to Pr.01-12–01-19).
When Pr.02-09 is set to 1: the increasing / decreasing frequency command (F) operates
according to the setting of Pr.02-10 (0.001–1.000 Hz/ms).
Multi-function Input Response Time
Default: 0.005
Settings 0.000–30.000 sec.
Use this parameter to set the response time of the digital input terminals MI1–MI5.
This function is to delay and confirm the digital input terminal signal. The time for delay is also the
time for confirmation. The confirmation prevents interference that could cause error in the input to
the digital terminals. But in the meanwhile, it delays the response time though confirmation
improves accuracy.
Multi-function Input Mode Selection
Default: 0000
Settings 0000h–FFFFh (0: N.O.; 1: N.C.)
This parameter setting is in hexadecimal.
This parameter sets the status of the multi-function input signal (0: normally open; 1: normally
closed) and it is not affected by the status of SINK / SOURCE.
bit 0–bit 4 correspond to MI1–MI5.