UPDATING FIRMWARE
PSHD meter firmware is updated approximately twice a year in response to minor bug correction or
customer requested features. Documentation is expected to be downloaded and used together within a
“Media Release” which includes firmware, ViewPoint HD Updates, register list updates, and manual
updates. Mix and match operation of components between separate Media Releases is not
recommended. The basic updating procedure is as follows:
1) Download the Latest Media Distribution (from the DENT website) and review the change
log.
2) Un-install and Re-install ViewPoint HD software (ViewPoint HD uninstallation directions
can be found in the Meter Configuration section of this guide.)
3) Locate the appropriate binary file within the Firmware folder of the Media Release
(example below)
4) Connect to the meter using ViewPointHD and locating the “Firmware Update” utility
window on the Advanced tab.
5) Press the “File Finder” and locate the model appropriate binary file (HD03,HD12 …)
6) Press the “Upgrade” button and Acknowledge the warning
7) Observe the Progress of the File Transfer into Flash memory.