EasyManuals Logo

Eaton 9PXM User Manual

Eaton 9PXM
130 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #80 background imageLoading...
Page #80 background image
66 4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 09
15. The UPS front panel display automatically turns on whenever input power is present and at least one
power module is installed. Set up the initial operating parameters through the front panel display (see
6.5 Initial Startup Parameters ).
16. If applicable, test proper operation of optional external control signals and computer communication before
connecting the load.
17. If there are receptacles on the UPS rear panel, plug the equipment to be protected into the UPS output
receptacles.
NOTE DO NOT protect laser printers with the UPS because of the exceptionally high power
requirements of the heating elements.
18. Turn on the equipment that is connected to the UPS.
19. If there is an external bypass switch, turn it to UPS. Otherwise, close the load distribution circuit breaker
(s).
66..44 SSttaarrttuupp ffoorr UUnniittss iinnssttaalllleedd wwiitthh aa BBPPEE TTyyppee SSwwiittcchh
1. If your unit is wired to an external bypass switch, you must perform a voltage and phase check (Steps 2
through 13). Otherwise, skip to Step 14.
CAUTION
Before operating the bypass switch, use the following procedure to check the wiring for correct installation. To
prevent damage to the load, turn off the main circuit breaker in the load service panel or verify that the load
cannot receive power from the UPS.
2. At the bypass switch, press the red button and turn the switch to UPS.
3. Remove the six screws in the bypass switch front cover and remove the cover to gain access to the
terminal block for voltage measurements.
4. If external battery cabinets are installed, close the DC emergency disconnect switch button on the back of
each external battery cabinet. Insert the switch key supplied with the cabinet into the button and turn
clockwise 1/2-turn. Pull the button out to close the switch. Turn the key back counter-clockwise, and
remove the key.
5. The UPS front panel display automatically turns on whenever input power is present and at least one
power module is installed. Set up the initial operating parameters through the front panel display (see
6.5 Initial Startup Parameters ).
6. Use an AC voltmeter to measure voltages on the terminal block inside the bypass switch cabinet. See
Figure 19 , which shows the terminal numbering for input and output UPS connections.
7. Record your measurements in the following chart. The voltages in the first column should be nearly equal
to the voltages in the second column. If the values differ by more than a few volts, check the terminal
block connections and correct any wiring problems.
AC Line input Measurement AC from UPS Output Measurement
L1 to L2 (11 to 12*) 7 to 8*
N to L1 (10 to 11*) 6 to 7*
N to L2 (10 to 12*) 6 to 8*
* For some installations, there is no connection at terminals 6, 8, 10, or 12.
Startup for Units installed with a BPE Type Switch

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 9PXM and is the answer not in the manual?

Eaton 9PXM Specifications

General IconGeneral
TopologyDouble Conversion Online
Battery TypeValve-Regulated Lead Acid (VRLA)
Power Factor0.9
Frequency50/60 Hz
EfficiencyUp to 96%
Input Voltage208/220/230/240 VAC (single-phase); 208/400/415 VAC (three-phase)
Output Voltage208/220/230/240 VAC (single-phase); 208/400/415 VAC (three-phase)
Communication PortsUSB, RS-232, Optional Network Card
Operating Temperature0 to 40°C
WeightVaries by model
DimensionsVaries by model

Related product manuals