Eaton Remote Power Panel (RPP) User’s Guide 164202125—Rev 5 www.eaton.com/powerquality 3
Chapter 2 Safety Warnings
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and maintenance
of the Eaton Remote Power Panel (RPP). Please read all instructions before operating the equipment and
save this manual for future reference.
The RPP is designed for industrial or computer room applications, and contains safety shields (interior
barriers) behind the doors. However, the EMS-RPP system is a sophisticated power system and should
be handled with appropriate care.
DANGER
The RPP contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED
SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the RPP with the
exception of adding and wiring branch circuit breakers.
WARNING
l
RISK OF ELECTRIC SHOCK. The electrical enclosure of this unit must be bonded to the Building
Grounding Electrode for safe operation. Do not use the isolated ground feature without bonding the
RPP enclosure to the Building Grounding Electrode.
l
RISK OF ELECTRIC SHOCK. This unit may receive power from more than one source. Disconnect all
AC sources before servicing
l
To reduce the risk of fire or electric shock, install this RPP in a temperature and humidity controlled,
indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40C
(104°F). Do not operate near water or excessive humidity (95% maximum). The system is not
intended for outdoor use.
l
Ensure all power is disconnected before performing installation or service.
l
As a result of the connected loads high leakage current is possible. Connection to earth ground is
required for safety and proper product operation.
CAUTION
l
Keep the RPP doors closed to ensure proper cooling airflow and to protect personnel from dangerous
voltages inside the unit.
l
Do not operate the RPP close to gas or electric heat sources.
l
Locate the RPP on concrete or other non-combustible surface only.
l
The operating environment should be maintained within the parameters stated in this manual.
l
Keep surroundings uncluttered, clean, and free from excess moisture.
l
Use leveling feet only for distributing the weight of the cabinet equally. Using the leveling feet to raise
the cabinet may result in serious injury to personnel or damage to the cabinet.
l
Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the
equipment.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton Remote Power Panel and is the answer not in the manual?

Eaton Remote Power Panel Specifications

General IconGeneral
BrandEaton
ModelRemote Power Panel
CategoryPower distribution unit
LanguageEnglish

Related product manuals