Section 3: Initial control programming
This section explains each step for properly completing initial
control programming settings on a CL-6 voltage regulator
control and back panel. Check the System Line Voltage rating
on the regulator nameplate. Refer to the regulator service
manual as identified on the regulator nameplate for addi-
tional information on the regulator.
This section covers standard set-up procedures
for controls, including control replacement. Refer to
Programming and Reconfiguring for Different
Voltage Systems, in this section of this manual, when
installing/replacing the CL-6 control and reconfiguring the
regulator for a different voltage system.
1. Start with all switches on the control front panel turned
Off.
2. There are two options for powering the control: internal
power or external power. Select one method and follow
the appropriate step.
A. Internal Power
Turn POWER switch to Internal from the Off position.
B. External Power
Apply external source to EXTERNAL SOURCE
binding posts: hot lead to black, top binding posts;
neutral lead to white, bottom binding posts; ground
to green ground binding posts. See detailed
instructions for applying power to the external source
terminals in Section 1 of this manual.
Turn POWER switch to External from the Off
position.
Basic programming
Complete the steps in Table 3-1 (on the next page) to
program the control for basic operation. Continue with the
steps in Table 3-2 to then program the control for additional
features or control replacement. For each item, check each
value and verify or change as appropriate.
Note: After turning on the control and the LCD displays
PASS, press Escape for further keypad use.
Step-by-step instructions are included in Tables 3-1 and
3-2. The Instructions column lists keys to press (i.e.; Enter,
Edit, 7, etc.). Also, italicized instructions denote a choice
or an entry; Value denotes a desired value entered via the
numeric keypads; and following each “Scroll” is an italicized
list of alternatives that appear in the display, within that
function code. Scroll through the list until the desired alter-
native is selected, and then press Enter.
Perform a Demand Master Reset (FC 38) after completing
the initial control programming to reset to present demand
values.
Note: Go to FC 141 to change the language setting.
18
CL-6 SERIES CONTROL INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS MN225016EN January 2016

Table of Contents

Other manuals for Eaton Tandem ELF Current-Limiting Dropout Fuse

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton Tandem ELF Current-Limiting Dropout Fuse and is the answer not in the manual?

Eaton Tandem ELF Current-Limiting Dropout Fuse Specifications

General IconGeneral
BrandEaton
ModelTandem ELF Current-Limiting Dropout Fuse
CategoryCables and connectors
LanguageEnglish

Related product manuals