FB3000 RTU Instruction Manual
D301851X012
November 2023
44 Installation
2.11.5 Connecting a serial port to a Rosemount 4088B
Transmitter (3SRSG4)
You can wire any of the four serial ports for communication with a Rosemount 4088B
transmitter using RS-485 (2-wire).
When connecting a COM port to a Rosemount 4088B transmitter follow this
configuration:
Figure 2-34. COMn Configured for RS-485 (2-wire) Connection to a Single Rosemount
4088B Transmitter
Enable AC termination using switches
RS-485 bus; twisted pair required
Connect cable shields to suitable Instrument Earth connection point
Notes
For COM1, n=1, pin numbers as follows: a=1, b=2, c=3, d=4, e=5
For COM2, n=
2, pin numbers as follows: a=6, b=7, c=8, d=9, e=10
For COM3, n=3, pin numbers as follows: a=11, b=12, c=13, d=14, e=15
For COM4, n=4, pin numbers as follows: a=16, b=17, c=18, d=19, e=20