FB3000 RTU Instruction Manual
D301851X012
November 2023
50 I/O Configuration and Wiring
Figure 3-2. Analog Input (AI) Wiring Using Loop Power
1
External current source
3.1.2 Analog Outputs (3MIX12/3MSG12)
The 12-channel mixed I/O module includes two dedicated analog output channels, with
the following characteristics:
Table 3-3. Analog Output Characteristics
Type
Number
Supported
Characteristics
Analog Output
(AO)
2 dedicated
channels
4 to 20 mA range (or 1 to 5V) selectable within
FBxConnect.
Both analog outputs share a common ground.
You disable unused analog outputs to conserve
power.
Can be configured to fail either at last good
ou
tput value or as a preset value.