3 – 13
Section 3 • Installation
VSS/VSM/VSH/VSSH • Installation, Operation and Maintenance Manual • Emerson • 35391SD
Figure 3-10. Maximum Allowable Flange Loads
DISCHARGE
LINE
5 PIPE
DIAMETERS
CUSTOMER
SUPPORT
3-4 PIPE
DIAMETERS
SUCTION
LINE
X
Z
Z
Y
X
Y
CUSTOMER
SUPPORT
DISCHARGE
LINE
5-6 PIPE
DIAMETERS
CUSTOMER
SUPPORT
3-4 PIPE
DIAMETERS
SUCTION
LINE
X
Z
Z
Y
X
Y
HANGER
CHECK
VALVE
HANGER
CHECK
VALVE
CUSTOMER SUPPORTS
WHEN CHECK VALVE
IS MOUNTED HERE
CUSTOMER SUPPORTS
WHEN CHECK VALVE
IS MOUNTED HERE
5 PIPE
DIAMETERS
5 PIPE
DIAMETERS
CHECK
VALVE
Nozzle Dia. (in.) Fz (lbf) Fy (lbf) Fx (ft-lbf) Mzz (ft-lbf) Myy (ft-lbf) Mxx (ft-lbf)
4 400 400 400 300 300 300
6 600 600 600 500 500 500
8 900 900 900 1000 1000 1000
10 1200 1200 1200 1200 1200 1200
12 1500 1500 1500 1500 1500 1500
14 2000 2000 2000 2000 2000 2000
Table 3-1. Maximum Allowable Flange Loads
may be drained from the system after the plant has
been shut down in cold weather. These precautions
will avoid costly damage to the equipment due to
freezing.
This information is taken from ASHRAE 15-89 and ANSI/
ASME B31.5. The installing contractor should be thor-
oughly familiar with these codes, as well as any local
codes.
CAUTION
Accumulated liquid in the suction header can damage
the compressor if not drained. Always drain headers
(suction and discharge headers) prior to start-ups.
Failure to comply may result in damage to equipment.
Flange Loads
The ideal load applied to anges of the compressor unit
is zero. However, it’s not practical to expect that no loads
will be applied to unit connections. Thermal, dead, live,
wind & seismic loads must be considered and even toler-
ated. Well supported external piping connected to the
compressor will still result in some loads applying forces
and moments in three axes to unit anges.
The most important issue is the motor-compressor mis-
alignment caused by external forces (F in lbf) and mo-
ments (M in ft-lbf) imposed by plant piping. In Figure
3-10 and Table 3-1, are the maximum allowable forces
and moments that can be applied to compressor anges
when the compressor is mounted on an oil separator.
It must be noted that it is necessary to check for com-
pressor shaft movement when the job is complete. In
no case shall the attached piping be allowed to cause

Table of Contents

Other manuals for Emerson Vilter VSS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Vilter VSS and is the answer not in the manual?

Emerson Vilter VSS Specifications

General IconGeneral
BrandEmerson
ModelVilter VSS
CategoryAir Compressor
LanguageEnglish

Related product manuals