Instruction Manual
D103409X012
Detailed Setup
May 2013
67
Alert Record
Field Communicator
HC, AD and PD
Configure > Detailed Setup > Alert Setup > Alert Record (1‐2‐3‐6)
ODV
Configure > Detailed Setup > Alert Setup > Alert Record (1‐2‐3‐7)
To be recorded, an alert must both be enabled for reporting, and the group in which it resides must be enabled for
recording. Table 4‐7 lists the alerts included in each of the groups. When any alert from an enabled group becomes
active, active alerts in all enabled groups are stored.
Table 4‐7. Alerts Included in Alert Groups for Alert Record
Alert Group Alerts Include in Group
Valve Alerts
Travel Lo Alert
Travel Hi Alert
Travel Lo Lo Alert
Travel Hi Hi Alert
Travel Deviation Alert
Drive Signal Alert
Failure Alerts
Flash ROM Fail
No Free Time
Reference Voltage Fail
Drive Current Fail
Critical NVM Fail
Temperature Sensor Fail
Pressure Sensor Fail
Travel Sensor Fail
Miscellaneous Alerts Auxiliary input
Alert Record has Entries Enable—Yes or No. When enabled indicates when an alert has been recorded. Factory default
is Yes.
Alert Record Full Enable—Yes or No. When enabled indicates when the Alert Record is full. Factory default is Yes.
View Alert Records—Displays all recorded alerts and the date and time the alerts were recorded.
Clear ALL Records—Clears the alert record. To clear the alert record, all alerts in enabled groups must be inactive.
Alert Groups
DFailure Group Enable—Permits enabling the Failure Alert group. Table 4‐7 lists the alerts included in each of the
groups. Factory default is Yes.
DValve Group Enable—Permits enabling the Valve Alert group. Table 4‐7 lists the alerts included in each of the groups.
Factory default is Yes.
DMiscellaneous Group Enable—Permits enabling the Miscellaneous Alert group. Table 4‐7 lists the alerts included in
each of the groups. Factory default is No.

Table of Contents

Other manuals for Fisher FIELDVUE DVC6200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fisher FIELDVUE DVC6200 and is the answer not in the manual?

Fisher FIELDVUE DVC6200 Specifications

General IconGeneral
BrandFisher
ModelFIELDVUE DVC6200
CategoryController
LanguageEnglish

Related product manuals