Table 17: Communication modes
Function Default Description
Phone 1 report
mode
Off
Phone 2 report
mode
Off
Phone 3 report
mode
Off
Phone 4 report
mode
Off
Determines how the panel sends a report to the central station
for each of the phone numbers programmed.
The options are: All SIA, All CID, Alarm SIA, Alarm CID, Nonalarm
SIA, Nonalarm CID, backup SIA (phone failure backup), Backup
CID (phone failure backup), Voice dialer, Off
Alarms include: Fire, Intrusion, Emergency, Silent, and Alarm Cancels.
Nonalarms include: Latchkey, No Activity, Openings, Closings, Fail-to-Open, Fail-to-
Close, Force Armed, AC Power Failure, CPU Low Battery, and Trouble Restoral.
Timers
Table 18 below describes the Timers menu.
Table 18: Timers menu
Function Default Description
Latchkey time Off Determines whether the panel reports a latchkey alarm if the
system is not disarmed at a preset time between midnight and
11:59 p.m. (on). If the latchkey feature is disabled (off), the panel
will not report a latchkey alarm. The system clock must be set
for the latchkey feature to work.
Entry delay 030 seconds Determines how much time you have to disarm the system
after entering the armed premises through a designated delay
door, before an alarm occurs. Beeps sound during the entire
delay time to remind you to disarm the system. When turned
on, the entry delay can be set from 030 to 240 seconds.
Exit delay 060 seconds Determines how much time you have to leave the premises
through a designated delay door after arming the system.
Beeps sound after arming the system to remind you to leave
the armed premises. If a delay door is opened after the exit
delay expires, the entry delay begins. If you arm the system
with no delay and open a delay door after the exit delay
expires, an alarm occurs.
No activity tm Off Determines whether the panel sends a no activity report to a
central station when the programmed time elapses (on), or if
the feature is disabled (off). No activity means the control
panel, remote handheld, and key-chain touchpad buttons have
not been pressed and sensors have not been tripped within a
specified time (except sensors in group 25 and 43). The timeout
can be set from 02 to 24 hours.
Simon XT Installation Manual 35