EasyManuals Logo
Home>Grant>Solar panel>GSD1

Grant GSD1 User Manual

Default Icon
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
Figure 120: Flush/Fill Valve Closed -
For Filling
14.3 Filling and Flushing the
System
Heat Transfer Fluid
Blue non-toxic heat transfer fluid
Practically odourless based on 1.2
propylene glycol
Good corrosion inhibitor
Remains stable over long period of
time
Nitrate, phosphate and ammonia free
40% solution of propylene glycol in
water
Supplied ready mixed in 10 or
20 litres containers
Filling and Flushing Valves
The stop valves on the flush/fill
valve assembly are used for filling
and flushing the solar thermal
installation.
To enable filling/flushing, the slot in
the flush/fill valve spindle must be in
the horizontal position. See Figure
120.
Important:
The collectors must be cool
before filling the system can
commence. The collectors must
be covered, to stop solar
radiation reaching them, until
completion of the filling and
commissioning procedure.
Filling the System
Before filling the system, check the
expansion vessel charge pressure and
adjust as required. Refer to Table 10.
Connect pressure hose to the filling
valve connection and open the
valve
Connect the flushing hose to the
flushing valve connection and open
the valve
Using a slotted head screwdriver,
close the flush/fill valve. Refer to
Figure 120
Fill the filling station tank with
sufficient solar fluid for the system
Check that Flow and Return ball
valves are set half open. Refer to
Figure 114
Using filling station, fill the solar
circuit and then flush for approx.
15 minutes
When the filling pump is running,
close the flushing valve and set the
system pressure to around 4 - 5 bar
When the pressure is reached, close
the filling valve and immediately
switch off the filling pump
Check that the device is leak-free.
If the pressure gauge shows a
significant drop in pressure, this
points to a leakage in the system
Re-open the flush/fill valve
Switch on the circulating pump
(control position “manual”) to the
highest pumping level (III) and allow
it to circulate for at least 15 minutes
Set the controller to “stand by”
(pump = OFF) and then bleed the
system using the hand ventilator on
the air jet until the heat transfer fluid
begins to escape
Set the operating pressure (as in
Table 10) by carefully opening the
flushing valve and releasing the fluid
into the catchment tank of the filling
pump
Switch on the circulating pump
(controller set to manual)
Set the flow rate on the flow
indicator (as in Table 11) by
selecting the appropriate pump
speed (I, II or III) and by using the
flush/fill valve
Remove the hoses from the filling
connections and screw the caps on
the filling and flushing valves.
Release the flushing valve first and
then the filling valve
Note:
Now switch the controller to
automatic operation
Figure 121: Flush/Fill Valve Open -
For Normal Operation
Figure 119: Heat Transfer Fluid
Filling Connection
Flush/Fill Valve
Flushing Connection
Commissioning
the System
57
For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk - info@mytub.co.uk 0844 556 1818

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grant GSD1 and is the answer not in the manual?

Grant GSD1 Specifications

General IconGeneral
BrandGrant
ModelGSD1
CategorySolar panel
LanguageEnglish

Related product manuals