Installation height in meter Minimum room size in m
2
1,80 7,0
1,85 6,6
1,90 6,3
1,95 6,0
2,00 5,7
2,05 5,4
2,10 5,2
2,15 4,9
2,20 4,7
2,25 4,5
2,30 4,3
2,35 4,1
2,40 3,9
2,45 3,8
2,50 3,6
2,55 3,5
2,60 3,4
2,65 3,2
2,70 3,1
2,75 3,0
2,80 2,9
2,85 2,8
2,90 2,7
2,95 2,6
3,00 2,5
HC R-290 Refrigerant Charge 0,200 kg
Table of various installation height and resulting room size.
The Installation Site - general information
The system should not be mounted at the following sites because of the existing
danger of outer influences for a risk of malfunction or failure. In cases when in-
stallation to these sites is unavoidable, first contact the GREE Co. service part-
ner.
1. Places with strong heat sources, combustible gases, vapours or volatiles
2. Places evoking high frequency waves, e.g. by radio equipment, medical or
welding equipment
3. Places with an unusually high salt content in the air
4. Places with oil containing air
5. Places next to hot sources or geysers because of sulphite gases could be
dissolved in the air
6. Any other places with specific but comparable conditions to those men-
tioned above. In case of any doubts refer to the manufacturer or to an
authorised service centre.
European stan-
dard EN378-1
International
Standard
IEC 60335-2-40