TAKING CARE OF UNEXPECTED PROBLEMS
NO POWER AT THE AC RECEPTACLES
NO POWER AT THE DC TERMINALS
Possible Cause Correction
AC circuit breaker left in the
OFF position after starting.
Switch AC circuit breaker ON (see
page 32).
GFCI system activated. GFCI receptacle
(120 V 20 A duplex receptacle):
Test GFCI and press the RESET
button (see page 29).
Replace or repair power tool or
appliance.
AC circuit protector tripped. Check AC load and reset AC
circuit protector (see page 15).
Faulty power tool or
appliance.
Replace or repair power tool or
appliance.
Stop and restart the engine.
Internal circuit overheated. Stop the engine. Reduce the
electrical load. Wait a few
minutes for the internal circuit to
cool down. Restart the engine.
Faulty generator. Take the generator to an
authorized Honda servicing
dealer, or refer to the shop
manual.
Possible Cause Correction
DC circuit protector OFF. Turn DC circuit protector ON
(see page 17).
Faulty generator. Take the generator to an
authorized Honda servicing
dealer, or refer to the shop
manual.
31Z236120.book 71 ージ 015年12月10日 木曜日 午前11時43分

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honda EM4000SX and is the answer not in the manual?

Honda EM4000SX Specifications

General IconGeneral
BrandHonda
ModelEM4000SX
CategoryInverter
LanguageEnglish

Related product manuals